30
Function: State output
according to signal faults
NO
NC
active
inactive
Work State
Whenever an error or an alarm occurs, the signal can
be sent with this output selected.
Any fault (Error, Alarm or power loss) can be sent to a
remote control or alarm system.
Parameters that can be set:
trigger:
[any status (Error, Alarm or power loss)]
Select contact logic:
[NO] or [NC]
(factory setting: NO)
10.4.2
Serial communicatiopn outputs
Modbus RTU
For a list main communication parameters see Appendix 11.2, page 32.
For a complete communication table with address and data type please contact the area sale
manager for details.
Factory setting:
RS485:
Modbus RTU:
Baud rate
9600
Parity
none
Address
1
M-Bus RTU
For a list main communication parameters see Appendix 11.3, page 33.
For a complete communication table with address and data type please contact the area sale
manager for details.
Factory setting:
RS485:
M-Bus RTU:
Baud rate
2400
Address
0