Hydromate 20 —
identification of controller and settings
1.
Using a slotted screwdriver turn the
‘
Rotary dial
’
to the selected Flush
program. (See table 1 below)
2.
Before setting the fill time the cistern must be empty. NB: If the cistern is
not completely empty at this stage, you will need to carry out steps 5 and 6
twice.
3.
Activate the 230v supply and press the reset button. The LED will illuminate
green/red/amber and both relays will click. The Hydromate will enter setup
mode and will click within 20/30 seconds. In this state the unit is ready to
set fill time, flashing red/amber
4.
Press the Fill Time button once. The solenoid valve will open and allow water
to flow into the cistern. Amber LED will flash while setting fill time. When the
cistern begins flushing, press the Fill Time button again to close the valve.
Your Hydromate is now set and will be armed in 50 seconds.
5.
PIR will illuminate green on each detection, once set.
Solenoid Valve Connections
Valve
2
1
230v
supply
Flush Frequency
Rotary Dial
Table 1
Hydromate 20
No of
Bowls/
Places
Select
Flush
Program
Flush Delay
Hygiene
Flush
Notes
1
1
30 mins
24 hrs
2
2
40 mins
24 hrs
3
3
25 mins
24 hrs
4
4
30 mins
24 hrs
5
5
25 mins
24 hrs
6
6
20 mins
24 hrs
Any
7
80 to 40 mins
72 hrs
Eco
-
Pro
Arena 1
8
10 mins
48 hrs
Arena/Theatre
Arena 2
9
15 mins
72 hrs
Arena/Theatre
T3
0
5 mins
24 hrs
Test
Arena 1 & 2 Intensive use venue