Page - 29
Figure 4
1. Deactivate power to heat pump.
2. Remove heat pump electrical access panel.
3. Route 22-gauge (minimum), 2-conductor, low-voltage wires from the
controller to the low voltage side of the heat pump's electrical
enclosure. Follow all National Electric Codes (NEC) unless State or
Local guidelines supersede.
4. Connect the controller wires to the microprocessor port labeled "Ext
Controller" with the terminals labeled "Y" and "Z" as follows. See
Figure 4.
l
Connect one wire to “Y”.
l
Connect other wire to “Z”.
l
The polarity of the wire is not important.
5. Reattach heat pump access panel.
6. Apply power to heat pump.
7. Configure the heat pump to accept a 2-wire external controllers signal as shown. See "
Configure 2-wire controller
Enter "Installer Menus", then proceed
1
-
Ins
ta
ll
at
ion
Summary of Contents for Leisure Temp LT1000
Page 2: ......
Page 9: ...Page 6 1 3 Dimensions Leisure Temp LT55 Leisure Temp LT400 1 Installation...
Page 10: ...Page 7 Leisure Temp LT600 Leisure Temp LT700 LT800 1 Installation...
Page 26: ...Page 23 Configure Call Flex Enter Installer Menus then proceed 1 Installation...
Page 30: ...Page 27 1 Installation...
Page 33: ...Page 30 1 Installation...
Page 36: ...Page 33 Configure for 24 Hour Mode Enter Installer Menus then proceed 1 Installation...
Page 37: ...Page 34 Configure for Scheduled Mode Enter Installer Menus then proceed 1 Installation...
Page 38: ...Page 35 1 Installation...
Page 41: ...Page 38 1 Installation...
Page 43: ...Page 40 1 Installation...
Page 46: ...Page 43 1 Installation...
Page 50: ...Page 47 1 Installation...
Page 53: ...Page 50 1 Installation...
Page 55: ...Page 52 1 Installation...
Page 72: ......