5
4.
Controlling
Adjustion of set point:
•
Turn key 3 to „SET “(nominal value). Adjust key 4 (set point adjustion) to the nominal value.
•
Turn switch 3 back to „mV” (measuring). The unit is now ready to use. As soon as the actual mV-value
drops below the adjusted set point, the plug (6) is activated.
5.
Troubles
- The unit shows wrong values – clean electrode.
- Redox potential electrodes have only a limited lifespan – depending on use, between 1 and 3 years.
6.
Technical data:
Display:
0.5" LED, 3.5 digits
Measuring range:
mV –1,000 up to +1,000
Resolution: 1 mV
Accuracy:
+1 mV (+ 1 digit)
Relay contact:
5 amps. at 100 - 240 V
Working temperature:
0 – 50 °C
Humidity:
below 80%
Control range: -500 up to +500 mV, digitally adjustable
Control accuracy:
+5 mV (+ 1 digit)
Power consumption: AC 100 - 240 V, 50 Hz, if not stated otherwise
Dimensions:
150 x 85 x 40 mm
Weight:
550 g
7.
Operation manual for Aqua Medic Redox potential electrode
The redox electrode is not included in shipment. It is, however, absolutely necessary for the function of the unit.
The Aqua Medic mV electrode with a plastic shaft is especially made for determing the redox potential in water.
It is used in aquaria, chemical industry, medicine and research laboratories.
7.1. Technical Data:
Measuring range:
-1,000 up to +1,000 mV
Sample temperature:
5 – 60 °C (short term)
Connection:
BNC–plug
Material:
plastic shaft, platinum
7.2. Measuring/Maintenance
- During the measuring, the platinum top has to be submersed in sample liquid.
- A new electrode or an electrode that has not been used for a longer time, has to be submersed for at least
24 hours.
8.
Warranty conditions
AB Aqua Medic GmbH grants the first-time user a 24-month guarantee from the date of purchase on all material
and manufacturing defects of the device. Incidentally, the consumer has legal rights; these are not limited by
this warranty. This warranty does not cover user serviceable parts, due to normal wear & tear ie: impellers or
drive wheels etc. The original invoice or receipt is required as proof of purchase. During the warranty period,
we will repair the product for free by installing new or renewed parts. This warranty only covers material and
processing faults that occur when used as intended. It does not apply to damage caused by transport, improper
handling, incorrect installation, negligence, interference or repairs made by unauthorized persons.
In case of
a fault with the unit during or after the warranty period, please contact your dealer. All further steps
are clarified between the dealer and AB Aqua Medic. All complaints and returns that are not sent to
us via specialist dealers cannot be processed.
AB Aqua Medic is not liable for consequential damages
resulting from the use of any of our products.
AB Aqua Medic GmbH
-
Gewerbepark 24 - 49143 Bissendorf/Germany
- Technical changes reserved – 02/2019