LEAKSHIELD
unlimited number of data sources to each export data set, the total number of ex-
port data sets is also unlimited.
11.
11.
11.
11. Page “LEAKSHIELD”
Page “LEAKSHIELD”
Page “LEAKSHIELD”
Page “LEAKSHIELD”
Click on the "LEAKSHIELD" device page below the "LEAKSHIELD" entry.
The most important LEAKSHIELD functions are visualized and triggered
on this page.
In the right view you see an overview page. In the upper area, the most important
information about LEAKSHIELD is displayed. This includes the current vacuum, the
required vacuum for protection against leakage, the status, the current fill level of
the reservoir and the current volume change in the system.
The "Mode" display informs you about the current operating mode of your LEAK-
SHIELD. By clicking on this area you can change the modes.
The following modes are available:
•
SHIELD
SHIELD
SHIELD
SHIELD (Complete protection by negative pressure and leak detection)
•
MONITOR
MONITOR
MONITOR
MONITOR (Low negative pressure, leak detection only)
•
RELEASE
RELEASE
RELEASE
RELEASE (System is switched off, automatic pressure compensation)
Below follows the an area „Action“ where you can select important device func-
tions directly by clicking on one of the symbols.
The following actions are available:
•
Test:
Test:
Test:
Test:
Test the cooling system for leaks
•
Measure fill level:
Measure fill level:
Measure fill level:
Measure fill level:
Measure the level in the reservoir.
•
Deaerate system:
Deaerate system:
Deaerate system:
Deaerate system:
Supports the venting of the system during filling
•
Refill system:
Refill system:
Refill system:
Refill system:
Suck coolant into the system
Depending on the currently selected action, the further display of the lower area of
this page changes.
In SHIELD and MONITOR mode, the middle area shows a diagram with the cur-
rent negative pressure and information on the minimum necessary negative pres-
sure, the current setpoint and the maximum negative pressure.
Below this is a diagram showing the pump running time per day. This serves as a
simple indicator for minor leakages. Tight systems should have a pumping time of
less than 15 seconds per day on average.