MODES OF OPERATION 

 
 

To Change Between Pool and Spa Set Points Automatically: 

This change can be done automatically as the water flow is either directed to the pool or spa.  The use of an 
external water pressure switch in the spa piping 

IS

 necessary.  A two-wire control circuit must be connected 

from the water pressure switch to terminals 18 and 19 on the electronic control board.  The red jumper wire 
at the top of the control board must then be cut to activate this system. 
 

Remote Thermostats and Controllers:  

If a remote thermostat or any other control system is to be used to turn the heater on and off, a normally open 
dry contact can be made at terminals 18 and 19 on the bottom right of the electronic control board.  The red 
jumper at the top of the control board must then be cut to activate this system.  In the case of a remote 
thermostat where the temperature will be regulated externally, set the Pool Mode to the OFF position and 
the Spa Mode to 104

°

F (40

°

C).  The heater will only run when the remote control calls for heating. 

 
 
  
 

 

        REMOTE SPA PRESSURE 

                            SWITCH OR AUTO  
                          CONTROLLER (N.O.

)

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

     2 METHODS CAN BE USED TO SWITCH UNIT BETWEEN POOL AND SPA MODE. 
          J-1 JUMPER - NOT CUT:  Using the select key will activate either mode manually. 
J-1 JUMPER - CUT:  A remote switch connected to terminals 18 and 19 will activate SPA MODE. 

 
 

RED JUMPER “J1” 

ELECTRONIC    

CONTROL 

BOARD 

18  19 

Summary of Contents for AC110

Page 1: ...LOW CONNECTIONS 2 3 ELECTRICAL CONNECTIONS 4 MODES OF OPERATION 5 WIRING DIAGRAMS 6 ELECTRONIC CONTROL PANEL 7 CHEMICAL USE 8 START UP 9 10 MAINTENANCE 10 11 TROUBLESHOOTING CHECKLIST 11 12 CALLING FOR SERVICE 12 WARRANTY 13 WARRANTY REGISTRATION 14 SAFETY CONSIDERATIONS Proudly Made in the USA support aquacomfort com www aquacomfort com service and support 888 475 7443 ALL IN GROUND MODELS INSTAL...

Page 2: ...the following Heater must be located outdoors Minimum of 24 of clearance on access service side of heater Minimum of 18 of clearance on all three air intake sides of heater Minimum of 48 of clearance for air discharge top of unit The heater should sit on a solid level surface sufficient above grade to prevent water from entering it and allowing condensate to drain from base The length of water pip...

Page 3: ...lowed run the filter pump and check the entire system for water leaks Make sure filter is clean and there are no obstructions in the filtering system Proper water flow is essential to the performance of your heater The minimum flow rate is 20 GPM TYPICAL WATER FLOW CONNECTIONS ...

Page 4: ... on left side of hinged electrical enclosure 3 Route weather tight flexible conduit through opening at base of unit Connect conduit to the bottom of the electrical enclosure using a weather tight fitting A knockout is provided next to the main contactor to accept a weather tight fitting Mounting conduit directly to the electrical enclosure will ensure a moisture tight seal extending the life of th...

Page 5: ...o turn the heater on and off a normally open dry contact can be made at terminals 18 and 19 on the bottom right of the electronic control board The red jumper at the top of the control board must then be cut to activate this system In the case of a remote thermostat where the temperature will be regulated externally set the Pool Mode to the OFF position and the Spa Mode to 104 F 40 C The heater wi...

Page 6: ...6 ...

Page 7: ...econds then revert back to the actual pool or spa water temperature Selecting Pool or Spa Mode Press the SELECT KEY until you reach P_S Pressing the UP or DOWN key will allow you to enter either POOL or SPA mode Green LED indicator lights will verify the mode selected FIL MODE MUST BE IN THE OFF POSITION OR A FLO3 ERROR CODE WILL BE DISPLAYED Selecting temperature in Fahrenheit or Celsius The fact...

Page 8: ...c chlorinators must be piped downstream from the heater A check valve must be installed between the chlorinator and heater to prevent raw chlorine from draining back into the heater A chemical trap may be piped at least six 6 inches above the chlorinator See piping diagram B Always maintain the following water quality requirements PH LEVEL 7 4 to 7 8 CHLORINE CONCENTRATION 1 to 5 PPM TOTAL ALKALIN...

Page 9: ...may require you to run your heater and filter pump continuously for at least 24 hours or more depending on the following factors Temperature difference between actual water temperature and desired water temperature Size of pool Ambient air temperature the cooler the air temperature the longer the heating time Heat loss evaporative convective radiative and conductive A pool cover solar blanket may ...

Page 10: ...water pressure switch will shut down the unit When normal water flow resumes the heater will automatically restart itself Other analyzer codes include FL3 LP3 LP dPO PO dPC Pc PLE CSE and SPi The TROUBLESHOOTING CHECKLIST on page 11 goes into further detail on these analyzer codes MAINTENANCE WARNING DISCONNECT ELECTRICAL POWER TO UNIT BEFORE STARTING ANY MAINTENANCE TO PREVENT SERIOUS INJURY FROM...

Page 11: ...re are no restrictions to its airflow Certain ambient air conditions may cause the heater to go into defrost mode displayed on the control panel as FS NOTE IT IS NORMAL FOR WATER TO DRIP FROM THE DRAINHOLES AT THE BASE OF THE HEATER THE UNIT PRODUCES CONDENSATE WHEN IT OPERATES Analyzer Codes FAILURE LOCK OUT This feature is for the protection of the heater If the same failure occurs three 3 times...

Page 12: ...l the error message disappears The control will be reinitiated to factory default Re enter the setpoints SPi Defective controller remove power and restart If error is still present replace controller CALLING FOR SERVICE Please eliminate any water flow problems before calling for service If you are unable to contact the installing agent please go to www aquacomfort com service and support to contac...

Reviews: