6. Trouble Shooting 

Use the table below to solve minor problems. 

Problem 

LCD/LED/Buzzer 

Explanation / Possible cause 

What to do 

When power fails, 
the backup time is 
shorten. 

Battery low alarm 
issue quickly. 

Battery voltage is too low. 

Charge  the  unit  at  least  8 
hours. 

Battery  capacity  is  not  full  even 
after charge the unit for at least 8 
hours. 

Check  the  date  code  of  the 
battery.  If  the  batteries  are 
too old, replace the batteries. 

Mains exist but the 
unit works in 
battery mode. 

Input voltage is 
displayed as 0 on the 
LCD and green LED is 
flashing. 

Input protector is tripped 

Check if AC breaker is tripped 
and  AC  wiring  is  connected 
well. 

Green LED is flashing. 

Insufficient quality of AC power. 
(Shore or Generator) 

1. Check if AC wires are too 
thin and/or too long. 
2. Check if generator (if 
applied) is working well or if 
input voltage range setting is 
suitable. 

(Narrow

Wide)

 

No LED display on 
the front panel 
when the utility 
power is normal. 

No LED display. 

Battery is not connected well. 

Check the external battery 
cable and terminal. Make sure 
all the battery connections to 
the unit are all correct. 

Battery defect.   

Replace the batteries. 

Buzzer beeps 
continuously and 
red LED is on. 

Fault code 00 

Output short circuited.   

Check if wiring is connected 
well and remove abnormal 
load.   

Fault code 01 

Overload error. The inverter is 
overload 110% and time is up. 

Reduce the connected load by 
switching off some 
equipment. 

Fault code 03 

Output voltage too high 

Return to repair center. 

Fault code 05 

Fan fault 

Replace the fan. 

Fault code 07 

Output voltage too low 

Return to repair center. 

If there is any abnormal situations occur, which doesn't list above, please call the service people immediately 
for professional examine. 
 

7. Specifications 

MODEL 

XP Pro 750 

XP Pro 1200 

XP Pro 2400 

CAPACITY 

525 W 

720 W 

1440 W 

INPUT 

Voltage 

230 VAC 

Voltage Range 

170-280 VAC (Narrow mode) 

90-280 VAC (Wide Mode) 

OUTPUT 

Voltage Regulation (Inv. 
Mode) 

+/-10% 

Transfer Time 

20 ms typical 

Waveform 

Simulated Sine Wave 

BATTERY & CHARGER 

Battery Voltage 

12 VDC 

24 VDC 

Floating Charge Voltage 

13.5 

VDC ±0.25 VDC 

27.0 

VDC ±0.5 VDC 

Max. Charge Current 

10A or 20A 

PHYSICAL 

Dimension (DxWxH)   

325 X 230 X 86 mm 

Net Weight (kgs) 

2.4 

2.5 

2.8 

 

Summary of Contents for Inverex XP Pro 1200

Page 1: ...Inverex Inverter V 1 0 Quick Guide...

Page 2: ...Table of Contents 1 Introduction 1 2 Important Safety Warning SAVE THESE INSTRUCTIONS 1 3 Product Overview 2 4 Installation 2 5 Operation 3 6 Trouble Shooting 8 7 Specifications 8...

Page 3: ...y cable reference according to system requirements CAUTION Do not disassemble the inverter Contact with the qualified service center when service or repair is required WARNING Provide ventilation to o...

Page 4: ...the battery terminal RED cable to the positive terminal BLACK cable to the negative terminal WARNING Please use the appropriate battery cable Please refer to Important Safety Warnings Section for the...

Page 5: ...alled press the power switch to turn on the unit The unit will work automatically in line mode or inverter mode according to input utility power s status When press the power switch again the unit wil...

Page 6: ...Voltage mode 11Vdc pcs 4 bars will flash in turns 11Vdc 11 5Vdc pcs Bottom bar will be on and the other three bars will flash in turns 11 5Vdc 12 5Vdc pcs Bottom two bars will be on and the other two...

Page 7: ...efined If User Defined is selected battery charge voltage and low DC cut off voltage can be set up in program 04 05 and 06 03 Max AC charging current 10A 20A default 04 Bulk charging voltage C V volta...

Page 8: ...age will be fixed to setting value no matter what percentage of load is connected Display Setting The LCD display information will be switched in turns by pressing SCROLL key The selectable informatio...

Page 9: ...utility Line Mode The unit will provide output power from the mains It will also charge the battery at line mode Charging by utility Battery Mode The unit will provide output power from battery Fault...

Page 10: ...the external battery cable and terminal Make sure all the battery connections to the unit are all correct Battery defect Replace the batteries Buzzer beeps continuously and red LED is on Fault code 00...

Reviews: