ALTENERGY POWER SYSTEM, INC.
17
WARNING:
Be aware that only qualified personnel should troubleshoot the
APS micro-inverter.
WARNING:
Never disconnect the DC wire connectors under load. Ensure that
no current is flowing in the DC wires prior to disconnecting. An opaque
covering may be used to cover the module prior to disconnecting the module.
WARNING:
Always disconnect AC power before disconnecting the PV module
wires from the APS micro-inverter. The AC connector of the first micro-inverter
in a branch circuit is suitable as a disconnecting means once the AC branch
circuit breaker in the load center has been opened.
WARNING:
The APS micro-inverter is powered by PV module DC power.
Make sure you disconnect and reconnect the DC connections to watch for the
three short LED flashes.
Troubleshooting a non-operating APS micro-inverter
To troubleshoot a non-operating APS micro-inverter, follow the steps below in order:
1.
Verify the utility voltage and frequency are within ranges shown in the in section 8
Technical Data of this manual.
2.
Check the connection to the utility grid. Verify utility power is present at the inverter
in question by removing AC, then DC power.
Never disconnect the DC
wires
while the micro-inverter is producing power.
Re-connect the DC module
connectors and watch for three short LED flashes.
3.
Check the AC branch circuit interconnection between all the micro-inverters. Verify
each inverter is energized by the utility grid as described in the previous step.
4.
Make sure that any AC breaker are functioning properly and are closed.
5.
Check the DC connections between the micro-inverter and the PV module.
6.
Verify the PV module DC voltage is within the allowable range shown in the Section
8 Technical Data of this manual.
7.
If the problem persists, please call APS Energy customer support.
WARNING:
Do not attempt to repair the APS micro-inverter. If
troubleshooting methods fail, please return the micro-inverter to your
distributor for replacement.
7.
Maintenance
No need to Maintenance.