background image

 

 

LSC

 
 

Installation check list 

 

Checkpoint 

Module 

Connectors  Installation 

Check 

Supply voltage 

Power supply   

 

 

Alarm voltage 

Power supply   

 

 

BM 

1/2 

 

 

Supply voltage (connection) 

RM 

1/2 

 

 

First 

Switch ON 1   

 

Termination resistor 

Last 

Switch ON 1   

 

Alarm  

BM 

8-15 

 

 

Alarm inputs - 

BM 

 

 

Horn acknowled 

BM 

 

 

Horn acknowledgement - 

BM 

 

 

Lamp acknowled 

BM 

 

 

Lamp acknowledgement - 

BM 

 

 

Lamp test + 

BM 

 

 

Lamp test - 

BM 

 

 

Relay output horn 

BM 

20/21 

 

 

Group alarm 

BM 

18/19 

 

 

Relay common alarm 

BM 

16/17 

 

 

Potential-free contacts 

RM 

8/9 – 22/23 

 

 

Connections 

All 

Bus 

 

 

Module address 

BM/RM 

 

 

 

Configuration 

 

 

 

 

 
 
 
 
 

Summary of Contents for LSC

Page 1: ...APS Annunciator System LSC Installation User Manual ...

Page 2: ...ings 7 CAN Bus 8 Installation check list 9 Basic Module BM 10 Application Characteristics 10 Function 10 Technical data 10 Wiring diagram 11 Relay Module RM 12 Application Characteristics 12 Function 12 Technical data 12 Wiring diagram 13 Panel Module PM 14 Application Characteristics 14 Function 14 Technical data 14 Wiring diagram 15 Bus connector CIM 15 Application Characteristics 15 Additional ...

Page 3: ...or the voltage supply and for the various inputs and outputs is connected to the terminals of the module The connection of the modules to each other is effected with factory made cables At its begin and end the BUS must be terminated with a resistor This termination resistor is on the Basic and Relay Module and it is connecting to the BUS with switch 1 on the modules The power circuit for the volt...

Page 4: ...4 LSC Connection principle ...

Page 5: ...r configuration via PC and expansion functions System components BM Basic Module Basic module with 8 signal inputs with RS232 interface Housing for DIN rail mounting RM Relay Module Expansion device with 8 relay outputs only RS232 interface Housing for DIN rail mounting PM Panel Module Optional module for external indication Front mounted CIM Connector Interface between system bus and building cab...

Page 6: ...e external wiring and the interaction with connected equipment Before testing take precautions that a possibly inadvertent activation of the outputs in association with equipment connected to them cannot lead to dangerous operating states When testing all inputs must be systematically activated in turn and the reaction of the system checked for its correctness Setting the module ID address Please ...

Page 7: ...her module LED blinking ID address LED blinking ID address 1 0 6 5 2 1 7 6 3 2 8 7 4 3 1 8 8 5 4 Factory settings Please refer to the following points to set a Basic Module BM back to factory settings o Turn of the supply voltage o Press and hold the two buttons lamp test and horn acknowledgement then turn on the supply voltage o The module acknowledges the restoration of the factory settings by b...

Page 8: ...or it is LED Bus LED Horn Type of the error Bus OFF The module has switched off the bus Possible reasons are a short circuit or a module operating with the same module ID address Connection error The module has no connection to the bus Bus conflict Several modules are using the same module ID address Failure neighbour module The next module has lost it s connection or does not work properly Steady...

Page 9: ...h ON 1 Termination resistor Last Switch ON 1 Alarm inputs BM 8 15 Alarm inputs BM 7 Horn acknowledgement BM 4 Horn acknowledgement BM 3 Lamp acknowledgement BM 5 Lamp acknowledgement BM 3 Lamp test BM 6 Lamp test BM 3 Relay output horn BM 20 21 Group alarm BM 18 19 Relay common alarm BM 16 17 Potential free contacts RM 8 9 22 23 Connections All Bus Module address BM RM Configuration ...

Page 10: ... horn annunciator relay is activated and the LED for this relay is illuminated After expiry of the set delay time the relays for collective alarm and group alarm are triggered and signalled with a LED in accordance with the operating mode set After the expiry of the preset delay time the fault is indicated at the alarm input by the blinking of the related LED Horn acknowledgement The integrated bu...

Page 11: ...11 LSC Wiring diagram ...

Page 12: ...ling o Integrated lamp test button o Built in LED showing the status of the supply voltage and the bus function Function The control of the Relay Module RM is effected via the internal BUS Optionally the alarm inputs can be linked with the individual outputs of the Relay Module OR linking of the alarm inputs Button lamp test All LED are activated for appr five seconds Outputs in BLINK mode are act...

Page 13: ...13 LSC Wiring diagram ...

Page 14: ... and common relay Function The PM has a red LED for each signal input of the BM Furthermore it has green LED for the system outputs The LED are illuminated when a signal input or a system output is active Horn acknowledgement The integrated buzzer and the relay contact for the horn are switched off Lamp acknowledgement LED goes out or changes to continuous light if the input is still activated Lam...

Page 15: ...teristics When you are using modules at different venues the CIM bus connector is the interface between the cabling The CIM provides a plug for the standard BCC cable on one side and cage clamp connectors on the other side The CIM can be clamped on a DIN rail ...

Page 16: ...ms ch Do not forget to make a safety copy after finishing your work Order overview 832 600 012 BM Basic Module 832 600 022 RM Relay Module 832 600 000 PM Panel Module 832 600 031 BCCS4 Bus cable 0 2m 4 poles 832 600 030 BCCS6 Bus cable 0 1m 6 poles 832 600 033 BCCL6 Bus cable 3 0m 6 poles 832 600 032 CIM Bus Connector DIN rail mounted 832 600 095 LSC configuration cable 832 600 903 Replacement ins...

Reviews: