CPS100 SERIES OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Adaptive Power Systems, Inc. (APS) • All Rights Reserved • No reproduction without written authorization from APS.
APS CPS100 Series Power Source Operation Manual
Page 177 of 231
Now press the Load soft key to load and
display the saved settings for this Master
unit.
Finally, press the Save soft key to store the
Master-Slave mode setting to non-volatile
memory. This unit is now ready to for use in
a Master/Slave configuration.
Note:
NEVER change the connections and
modes of Master and Slave units
while in multi-unit mode operation
as it could damage one of more
units.
Multi-Unit Modes of Operation
This section shows how two connect two or more CPS100 power sources into a specific
multi-unit configuration.
Note:
Make sure each unit used is configured for Master or Slave operation before
interconnecting them.
Note:
For configurations consisting of 3 or more units, it is strongly recommended to use 3
phase mains input provided 230V~ Line-to-Neutral (Europe/Asia) or 208V~ Line-to-
Line (US) which different phases feeding one unit. See diagrams on pages 182
through 186 for reference.