TAblE 2 – Troubleshooting Guide

Symptom

Possible Reason

Troubleshooting Procedure

Dehumidifier does not 

turn on/run.

No power to unit.

•   Check that the dehumidifier is plugged in.
•   Check that the power switch is turned ON.
•   Check that the control is turned ON.
•   Check that the circuit breaker has not tripped.

Dehumidifier blower is 

running but with little or 

no airflow.

Pressure drop across dehumidifier 

is higher than 0.6”w.c.

•   Check dehumidifier air filter and wash or replace.

Dehumidifier blower is 

running but compressor 

is not.

Float switch open.

•   If float switch installed, check connections at control board and empty condensate pan.
•   If no float switch installed check that the jumper is installed at the float switch terminals 

on the control board.

Coil frosting.

•   Lack of or reduced airflow. Check dehumidifier air filter and wash or replace.
•   Check that there is nothing blocking the inlet or outlet of the dehumidifier.
•   Inlet air conditions below 60°F. Increase the humidity setting.

Inlet air temperature is outside of 

the 50°F – 104°F range or the dew 

point is below 40°F and there is a 

demand for dehumidification.

•   No action. The compressor will not run if inlet conditions are out of range.

Dehumidifier is not 

draining properly.

Drain line blocked or unit not level. •   Verify that the unit is level.

•   Check the drain line blockages and for a continuous downward slope.

Dehumidifier is 

producing hot air.

Normal function.

•   Air is reheated across the condenser coil, resulting in a temperature rise between inlet 

and outlet.

TROUblESHOOTING 

(CONTINUED)

TAblE 1 – Diagnostic Codes (continued)

Diagnostic 

Code

Failure Mode

Action

Reset

E7

Float Switch Open

1.  Empty the condensate pan.
2.  Check the float switch connection at the control board.
3.   If not using a float switch, verify jumper is between float switch terminals on dehumidifier 

control board.

4.   If the problem persists, replace the float switch.

Self-Correcting

E8

Inlet Air Temperature 

Out of 50°F – 104°F 

range, or dew point 

below 40°F

1.   If temperature is out of range, no action, normal operation.
2.   If air temperature is between 50°F –104°F with a dewpoint above 40°F, contact Technical 

Support.

Self-Correcting

9

Summary of Contents for 1870F

Page 1: ...se ventilation to lower indoor humidity in the winter WARNING 1 120 Volts may cause serious injury from electric shock Disconnect electrical power before starting installation or servicing Leave power...

Page 2: ...n condensing Filter MERV 8 washable Airflow 310 CFM Table of Contents Safety Instructions 1 Specifications 2 Set Up Dehumidifier for Installation 3 Location Considerations 3 Drain Installation 4 Level...

Page 3: ...cient space for service on this side of the unit If locating the unit in an attic or crawl space a Model 76 Control mounted in the living space is recommended Refer to Model 76 Installation Instructio...

Page 4: ...oft tubing to curl up which may result in air lock Always install the dehumidifier in a condensate pan when locating in or above a finished space Adhere to local codes regarding draining of the conden...

Page 5: ...ny time if the humidity setting is lowered Your dehumidifier is equipped with two features that protect against unwanted energy consumption Defrost is a normal operating mode that helps to prevent sig...

Page 6: ...rm water and a mild detergent solution 5 Shake off the excess water from the filter 6 Replace the filter making sure the filter is secured in both the top and bottom filter rails 7 Replace the filter...

Page 7: ...crawl space sealed attic or other hard to access area a Model 76 can be installed in the living space and will operate as a remote control Refer to the Model 76 Installation Instructions and Owner s M...

Page 8: ...Terminal should be fully seated on the power board pins 2 Remove the side access panel and verify that the sensor is secured to the suction line 3 If the sensor is connected and secured to the refrig...

Page 9: ...ting Inlet air temperature is outside of the 50 F 104 F range or the dew point is below 40 F and there is a demand for dehumidification No action The compressor will not run if inlet conditions are ou...

Page 10: ...ss AA Deh 5571 6 Fan 130pt Deh with 8MFD Capacitor 5588 7 Wire Harness Power Deh 5454 No Part Description Part No 8 Sensor Low Temperature Deh 5455 9 Sensor High Temperature Deh 5456 10 Capacitor 50MF...

Page 11: ...S CORPORATION S LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OTHER THAN DAMAGES FOR PERSONAL INJURIES RESULTING FROM ANY BREACH OF THE AFORESAID IMPLIED WARRANTIES OR THE ABOVE LIMITED WARRANTY I...

Page 12: ...d in U S A 2015 Aprilaire A division of Research Products Corporation For product support contact Aprilaire at 1 800 334 6011 For sales inquiries contact Sylvane at 800 934 9194 or visit Sylvane com F...

Reviews: