Refrigerant Recovery Tips

Purging Non-Condensables from Recovery Cylinders

In the event that the Recovery Cylinder pressure is higher than expected, or if the recovery process 
seems slower than usual, use an external gauge (not the gauge on the recovery machine) and a 
Refrigerant Pressure/Temperature chart to check for the presence of non-condensable gases in the 
cylinder.

You can bleed/purge non-condensables into another cylinder following this procedure:

1. 

The Recovery Cylinder must remain undisturbed for at least 24 hours for the non-condensables to 
rise to the top of the cylinder.

2. 

Through a Manifold Gauge Set, connect the Recovery Cylinder Vapor Port to the Vapor Port of a 
second recovery cylinder.

3. 

Consult a Refrigerant Pressure/Temperature chart, and check the temperature of the Recovery 
Cylinder to determine what the pressure should be.

4. 

While the pressure is higher than the pressure on the chart, slowly open the Vapor Port to bleed off 
excess pressure until it is about 5 psi (0.35 Kg/cm

2

) above the pressure listed on the chart.

5. 

Close the valves and let the cylinder stand still for 10 minutes. Repeat if necessary.

80% Fill Weight

Refrigerant

Liquid Density 

@ 130ºF (

Lb/Ft

3

)

Fill 

Multiplier

Water

61.522

-

R-22

66.312

1.08

R-134a

67.46

1.10

R-404A

53.18

0.86

R-407C

62.28

1.01

R-410A

56.11

0.91

R-417A

62.383

1.01

R-417C

65.243

1.06

R-422A

58.343

0.95

R-422B

61.85

1.01

R-422C

59.174

0.96

R-422D

60.642

0.99

R-437A

65.231

1.06

R-438A

61.804

1.00

R-454B

51.343

0.83

Refrigerant recovery cylinders should only be filled to 80% of their 

maximum

 volume to allow for 

expansion during transportation. Recovery cylinder weight capacity is calculated by the manufacturer 
using water and given as 

Water Capacity

. Since refrigerant has a different density than water you 

must make a quick calculation to determine the 

maximum weight

 of refrigerant you can recover.

Stamped markings on the recovery tank indicate Tare Weight 
(

TW

) and Water Capacity (

WC

). The following equation should 

be used to calculate the maximum weight allowed in a cylinder.

WC x Fill Multiplier x 0.8 + TW 

= Max Total Tank Weight

See Page 4 for additional information

Example (R-22):

 

WC is 47.6Lbs, TW is 24Lbs.

47.6 x 1.08 x 0.8 + 24 = 

65.1 Lbs Total Tank Weight

(41.1Lbs of R-22)

Accounting for Hose Weight

The weight of recovery hoses should be taken into consideration during recovery and charging. Be 
sure to ‘tare’ the scale only after placing the cylinder on the platform 

and

 connecting hoses (to both 

tank and system). Also make note of the weight if hoses are removed at any point during the process.

WS260 OPERATION MANUAL

© 2019 APPION INC. - ALL RIGHTS RESERVED 

Summary of Contents for WS260

Page 1: ...COPYRIGHT 2019 APPION INC ALL RIGHTS RESERVED APPIONTM AND WS260TM ARE TRADEMARKS OF APPION INC WARNING TO REDUCE THE RISK OF INJURY OR PRODUCT DAMAGE READ OPERATION MANUAL PRIOR TO OPERATING PRODUCT www AppionTools com ...

Page 2: ...to field service work Aluminum construction creates a lightweight reliable platform and combined with advanced electronics creates a scale that is highly versatile on the job From critical charges measured in grams to large systems with hundreds of pounds of refrigerant the WS260 has the ability to handle whatever the next jobsite holds The built in display allows standalone use or connect to the ...

Page 3: ...NAL PROTECTIVE EQUIPMENT AND MSDS WS260 OPERATION MANUAL 2019 APPION INC ALL RIGHTS RESERVED HAZARD RISK TO BREATHING ASPHYXIATION DANGER Air and refrigerants pumped during refrigerant recovery may pose certain breathing hazards WHAT CAN HAPPEN HOW TO PREVENT IT Refrigerant vapors may be harmful or toxic when inhaled Use only in well ventilated areas In enclosed areas mechanical ventilation should...

Page 4: ... rely on these switches to prevent overfilling Only a refrigerant scale can provide an active and accurate measurement of the amount of refrigerant in the storage container Do not rely on these switches to stop the flow of refrigerant into the container Only the valves on the recovery machine and on the cylinder can stop the flow of refrigerant into the container Refrigerant expands when heated Di...

Page 5: ...rom the system The Zero function is used to clear the reading and store the weight of an empty platform Example Technician has noted that the scale does not read 0 0 lbs when unladen on a flat level surface External Power A USB Type C cable sold separately may be used to power the WS260 in cases where battery power is not sufficient or long term use is desired Remove the protective rubber plug on ...

Page 6: ...ivity is always enabled for ease of use and fast connections to your device If desired you can change the range Normal or Long Range in the main menu of the WS260 Note that changing to Long Range will reduce battery life but enable up to 984ft 300m line of sight connectivity Menu Items MODE RESOLUTION Three resolution modes are available Normal 10g 0 5 oz 0 1 lb resolution Ideal for most applicati...

Page 7: ...cale will record data A shorter interval will result in a more detailed log Select from 1 5 10 30 60 second intervals ERASE Activating this option erases the current data log and removes the data log symbol from the main screen Appion Central unlocks the full potential of the WS260 and is available on the App Store and Google Play Search for Appion or visit www AppionTools com to download the late...

Page 8: ...ter 61 522 R 22 66 312 1 08 R 134a 67 46 1 10 R 404A 53 18 0 86 R 407C 62 28 1 01 R 410A 56 11 0 91 R 417A 62 383 1 01 R 417C 65 243 1 06 R 422A 58 343 0 95 R 422B 61 85 1 01 R 422C 59 174 0 96 R 422D 60 642 0 99 R 437A 65 231 1 06 R 438A 61 804 1 00 R 454B 51 343 0 83 Refrigerant recovery cylinders should only be filled to 80 of their maximum volume to allow for expansion during transportation Re...

Page 9: ...at the sight glass is in good condition and does not leak CAUTION Preparing for Fast Refrigerant Recovery Every recovery procedure starts with the same four basics Remove any access valve cores from the AC R System access fittings with a Valve Core Removal Tool This removes restrictions that would otherwise limit the performance of the recovery machine and or cause overheating of the recovery cyli...

Page 10: ...b Accuracy 5g 0 10Kg 5g 0 03 of Reading Resolution Normal 10g 0 5 oz 0 1 lb High 1g 0 1 oz 0 01 lb or 10g 0 5 oz 0 1 lb Extended Battery Life 10g 1 oz 0 1 lb Wireless Range up to 984ft 300m line of sight Durability Rating IP65 Battery Life 150 hours High Resolution to 1200 hours Extended Battery Life Units Pounds Lb Lb Oz Oz Kilograms Kg Kg g Power Source 3 AAA Batteries USB C Operating Temperatur...

Page 11: ...ce in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception wh...

Page 12: ...on Inc 2800 South Tejon St Englewood CO 80110 USA Tel 1 303 937 1580 Fax 1 303 937 1599 www AppionTools com Sales AppionTools com Support AppionTools com 2019 APPION INC ALL RIGHTS RESERVED OMXXXX EN 2019A ...

Reviews: