background image

4

GENERAL INFORMATION

What is a  beam detector? 

The XP95 beam detector is made up of  a    transmitter, 
a   receiver, an   interface and, optionally, one or more 
re

fl

 ectors.

The  trans mit ter projects a beam of modulated infra-red 
light to the  receiver which converts it to an electrical 
signal for process ing in the  interface.

The  trans mit ter and  receiver are mounted so that the 
beam will project ap prox i mate ly 0.3m to 0.6m below 
and parallel to the roof or ceiling level at distances 
up to 100m.  The maximum  lateral detection range is 
7.5m either side of the beam. The  interface is usually 
installed at ground level.

How does a beam detector work?

When smoke is present in the beam path the light reg-
istered by the  receiver is reduced by a level de ter mined 
by the density of the smoke.

In the event of the smoke obscuring the light by a pre-
selected minimum level for a period of 8 to 10 seconds 

fi

 re signal is generated.  The detection level can be 

set to 25%, 35%, 50% or 65% to suit different environ-
ments, examples of which are given in the table in the 
section  'Obscuration Level Setting' on page 6.

Automatic reset

If the beam detector has been in 

fi

 re or fault condition 

it will au to mat i cal ly  reset, once the 

fi

 re or fault is no 

longer present.  After a 

fi

 re condition there is a reset 

 delay of 30 seconds and after a fault a reset delay of 
3 seconds.

Automatic  signal strength 

Over a period of time the light registered by the  receiver 
might be reduced by factors such as dirt building up 
on the lenses of the detector.

The XP95 beam detector compensates for this auto-
matically in order to reduce the likelihood of unwanted 
alarms.  At the limit of  compensation the beam detector 
transmits a  fault signal.  In the event of a  

fi

 re  being 

detected when the beam detector has reached its 
compensation limit, the  

fi

 re signal will override the 

fault signal.

SYSTEM DESIGN

 Positioning beam detectors

The XP95 beam detector must be positioned correctly 
to minimise the detection time.  The detection time 
depends on

—the  location  of  the  beam  detector  within  the 

protected area

—the volume of smoke produced

—the con struc tion of the roof

—the  ventilation arrangements

Particular areas where beam detectors should 
not be 

fi

 tted include:

•  spaces where very high levels of ambient 

light are present in normal conditions

•  areas where excessive amounts of dust, 

smoke or water vapour are present as part 
of the normal environment

•  areas where rapid temperature changes 

occur

•  surfaces  subject to vibration or  movement

•  buildings in which it is not possible to 

mount the beam detector rigidly or align it 
correctly

When deciding where to install the beam detector, you 
need to think of the construction of the surface you 
are 

fi

 tting it to and to possible changes as a result, for 

example, of changing  seasons.  These surfaces must 
be solid and should not be subject to movement.

The maximum distance either side of the beam axis 
is typically 7.5m for satisfactory detection under 

fl

 at 

ceilings, providing a maximum total area coverage of 
1500 square metres (15m x 100m).  The maximum rec-
 om mend ed  installation height is 40m and the distance 
between the beam and the ceiling should be within 
0.3m and 0.6m (Fig 1).  No more than 3m of the beam 
path (measured from the centre of the beam) should 
be within 500mm of any wall or partitions. 

15m

30m maximum

45m and over

7.5m

7.5m

0.5m
 min

0.5m
 min

15m

15m

7.5m = max
beam to
wall
distance

0.5m = min
beam to
wall
distance

max = 40m

Fig 1

 

Positioning detectors under 

fl

 at ceilings—examples of three building widths

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for Smoke Detector XP95

Page 1: ...DETECTOR INSTALLATION GUIDE Apollo Fire Detectors 36 Brookside Road Havant Hampshire England www apollo fire co uk PP2079 2002 Issue 6 FIRE DETECTORS LIMITED www acornfiresecurity com www acornfiresec...

Page 2: ...the total obscuration signal 6 Setting the address 7 Address settings 7 Installing transmitter and receiver 8 Retro operation 9 Alignment and calibration 9 Aligning the beam detector 10 Calibrating th...

Page 3: ...sts Read the guide through once in order to understand the steps needed to install and align correctly Then when installing keep the guide handy and use it to find help on the subject you are currentl...

Page 4: ...fault signal In the event of a fire being detected when the beam detector has reached its compensation limit the fire signal will override the fault signal SYSTEM DESIGN Positioning beam detectors Th...

Page 5: ...es of practice A ceiling or roof with a slope in excess of 3 5 should be regarded as a pitched roof calculation it is recommended that not more than five beam detector sets are powered from each loop...

Page 6: ...ation signal Total obscuration is defined as obscuration of the beam to greater than 93 in 8 10 seconds The interface must be set so that either a fire or a fault signal is generated when this occurs...

Page 7: ...16 32 64 NORMAL OPERATION Address 1 ALIGNMENT MODE 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 91 41 42 43 44 45 46 47 48 49 50 51 52...

Page 8: ...ye Ensure that the transmitter is fitted so that access to the range potentiometer under the clear plug on the side is not impeded 4 Tighten both the receiver thumbwheel screws securely using a suitab...

Page 9: ...s been returned via a surface other than the reflectors Alignment and calibration The transmitter produces a conical beam of light which is approximately 3 metres in diameter at a distance of 100 metr...

Page 10: ...the LED to be visible over the entire beam length ie up to 100 metres During commissioning of the beam detector the LED will be in one of the following states Calibrating the beam detector The beam de...

Page 11: ...an be moved with slight resistance up down left and right 4 Remove the plug on the transmitter 5 Using a 0 point cross head or terminal screwdriver turn the potentiometer fully anti clockwise This adj...

Page 12: ...d if there is no flash after carrying out the movements described 11 Tighten the securing bolts and screws of the transmitter making sure it does not move and replace the plug covering the potentiomet...

Page 13: ...the HI and LO LEDs have extinguished If they have not the alignment procedure has to be repeated 13 Set segment 8 of the DIL switch on the interface to normal opera tion 64 No Op de www acornfiresecu...

Page 14: ...output in the interface is enabled The remote indicator output is useful in locations where the interface is not easily visible from the ground and confirmation of a fire signal is required Notes 1 Wh...

Page 15: ...and it is not possible to replace older versions with the enhanced version separately In such cases both interface and receiver must be replaced if a new receiver is to be installed The transmitter i...

Page 16: ...nsmitter not aligned with receiver Transmitter power too low No power to transmitter Receiver not pointing toward transmitter Interface alarm LED illuminated Beam is in alarm condition See notes Inter...

Page 17: ...Screened 4 core MICC for example 100m Finish White IP Rating 50 Operating temperature 200 C to 550 C Sizes and weights Interface 147 x 85 x 22 mm 200g Heads with Brackets 83 x 115 x 135 mm 400g each...

Page 18: ...18 FIRE DETECTORS LIMITED www acornfiresecurity com www acornfiresecurity com...

Reviews: