background image

5

How many XP95 beam detectors can be 
connected to a loop? 

Although the Apollo Beam Detector is loop powered, 
the total current drawn by the beam detector compo-
nents combined is considerably higher than a standard 
point detector (equivalent to approximately 40 point 
detectors). For this reason care must be taken when 
designing an analogue loop, bearing in mind the effects 
of voltage drop—a consequence of loop cable resist-
ance, device loading and control panel speci

fi

 cation.

Each beam detector set (consisting of  transmitter,  re-
ceiver and  interface) draws approximately 16mA from 
the analogue addressable loop and, unless proven by 

In buildings with  pitched roofs or ceilings the maximum 
distance either side of the beam 

in the  apex only

 may 

be increased by 1% for each degree of  ceiling pitch 
up to a maximum of 25% (Fig 2).

Example:  Roof pitch = 20°
 

Span of beam = 15m

 

15m + (15 x 20%) = 18m

There must be a clear line of sight between the   trans-
mitter and   receiver at all times.  If there is any doubt 
about the correct mounting of detectors in a particular 
installation, the position may be de ter mined by smoke 
tests.

All in stal la tions must conform to locally applicable 
stand ards and codes of practice.

A ceiling or roof with a slope in excess of 3.5° should 
be regarded as a pitched roof.

*calculation, it is recommended that 

not more than 

fi

 ve beam detector sets are powered from each loop 

or, alternatively, eight  interface/ receiver combinations 
when the  transmitter head is independently powered 
from a remote power supply.

Beam detectors must be protected by short-circuit iso-
lators.  For details of these please refer to Apollo PIN 
sheet PP2090.  For calculation purposes the  interface 
should be considered as 12 point detectors and the 
 transmitter 7 point detectors.

*Depending upon the type of panel used, the resist-
ance of cable and the total loop load, it may be pos-
sible to install in excess of 10 beam detector sets on 
a single analogue addressable loop.  A mathematical 
calculation to assess the worst case loop voltage drop 
should be performed prior to installation in order to 
prove the intended design. A loop voltage drop calcula-
tion program, known as ‘Loop Calculator’, has been 
developed by Apollo for use by system designers and  
is available as a free download from the Apollo web 
site (www.apollo-

fi

 re.co.uk).

10˚

7.5m

7.5+8.25m

8.25+7.5m

          

20˚

18m max

7.5 + 7.5 + 3.m

20˚

7.5m

15m

0.5m

Roof pitch = 20˚
Span of beam = 15m
15m + (15 x 20%) = 18m

Fig 2

 

Positioning detectors under different types of sloped or pitched roofs

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for Smoke Detector XP95

Page 1: ...DETECTOR INSTALLATION GUIDE Apollo Fire Detectors 36 Brookside Road Havant Hampshire England www apollo fire co uk PP2079 2002 Issue 6 FIRE DETECTORS LIMITED www acornfiresecurity com www acornfiresec...

Page 2: ...the total obscuration signal 6 Setting the address 7 Address settings 7 Installing transmitter and receiver 8 Retro operation 9 Alignment and calibration 9 Aligning the beam detector 10 Calibrating th...

Page 3: ...sts Read the guide through once in order to understand the steps needed to install and align correctly Then when installing keep the guide handy and use it to find help on the subject you are currentl...

Page 4: ...fault signal In the event of a fire being detected when the beam detector has reached its compensation limit the fire signal will override the fault signal SYSTEM DESIGN Positioning beam detectors Th...

Page 5: ...es of practice A ceiling or roof with a slope in excess of 3 5 should be regarded as a pitched roof calculation it is recommended that not more than five beam detector sets are powered from each loop...

Page 6: ...ation signal Total obscuration is defined as obscuration of the beam to greater than 93 in 8 10 seconds The interface must be set so that either a fire or a fault signal is generated when this occurs...

Page 7: ...16 32 64 NORMAL OPERATION Address 1 ALIGNMENT MODE 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 91 41 42 43 44 45 46 47 48 49 50 51 52...

Page 8: ...ye Ensure that the transmitter is fitted so that access to the range potentiometer under the clear plug on the side is not impeded 4 Tighten both the receiver thumbwheel screws securely using a suitab...

Page 9: ...s been returned via a surface other than the reflectors Alignment and calibration The transmitter produces a conical beam of light which is approximately 3 metres in diameter at a distance of 100 metr...

Page 10: ...the LED to be visible over the entire beam length ie up to 100 metres During commissioning of the beam detector the LED will be in one of the following states Calibrating the beam detector The beam de...

Page 11: ...an be moved with slight resistance up down left and right 4 Remove the plug on the transmitter 5 Using a 0 point cross head or terminal screwdriver turn the potentiometer fully anti clockwise This adj...

Page 12: ...d if there is no flash after carrying out the movements described 11 Tighten the securing bolts and screws of the transmitter making sure it does not move and replace the plug covering the potentiomet...

Page 13: ...the HI and LO LEDs have extinguished If they have not the alignment procedure has to be repeated 13 Set segment 8 of the DIL switch on the interface to normal opera tion 64 No Op de www acornfiresecu...

Page 14: ...output in the interface is enabled The remote indicator output is useful in locations where the interface is not easily visible from the ground and confirmation of a fire signal is required Notes 1 Wh...

Page 15: ...and it is not possible to replace older versions with the enhanced version separately In such cases both interface and receiver must be replaced if a new receiver is to be installed The transmitter i...

Page 16: ...nsmitter not aligned with receiver Transmitter power too low No power to transmitter Receiver not pointing toward transmitter Interface alarm LED illuminated Beam is in alarm condition See notes Inter...

Page 17: ...Screened 4 core MICC for example 100m Finish White IP Rating 50 Operating temperature 200 C to 550 C Sizes and weights Interface 147 x 85 x 22 mm 200g Heads with Brackets 83 x 115 x 135 mm 400g each...

Page 18: ...18 FIRE DETECTORS LIMITED www acornfiresecurity com www acornfiresecurity com...

Reviews: