COMMISSIONING
Analogue values
The beam detector returns a pre-set analogue
value corresponding to its status. These values
are defi ned in Table 4 below.
The beam detector may return a pre-alarm
value before a full alarm condition occurs. The
analogue value depends on the smoke density
and the set obscuration level (described on page
7) as shown in Table 5.
Analogue value
Signifi cance
0
Microprocessor fault
1
Sensor fault
2
Prism (refl ector) targeting mode
3
Alignment mode
4
General fault warning
5
‘Signal High’ fault
6
Contamination compensation limit reached
20
Alignment drift negative
25
Detector normal
30
Alignment drift positive
32
Contamination compensation level low (40%)
33
Contamination compensation level medium (60%)
34
Contamination compensation level high (80%)
45–54
Pre–Alarm values (see Table 5 below)
64
Alarm
Table 4
Analogue value returned
Actual obscuration at set
obscuration level of
25%
35%
50%
45
16
23
33
46
16
26
34
47
17
27
35
48
18
28
36
49
19
29
38
50
20
30
40
51
21
31
42
52
22
32
44
53
23
33
46
54
24
34
48
Table 5
Percentage of obscuration indicated by pre-alarm