Rev. B2, 7/15
DCR-1006A Level Controller
39
Automation Products Group, Inc.
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
• Specifications
Operating Voltage:
85-264 VAC
12-24 VDC (Nominal)
15-28 VDC (Operational)
9-28 VDC (4-20 mA Vs)
Housing:
PBT/Polycarbonate blend
Dimensions (in.):
6.25 x 3.125 x 2.25
Environmental Rating:
NEMA 6P
DST sensor Sample Rate:
80 to 1000 mS (programmable)
RST Display Resolution:
0.01 ft / 0.1” / 1 mm (unit dependent)
4-20 mA Output Accuracy:
min. +/- 0.25% of detected range (with no
temperature gradient)
Parameter Adjustments:
via push buttons, RS-485 interface to PC-based
APG Modbus Software via RST-6001, or RST-5000 series communications
module.
Operating Temperature:
-30 to 140
0
F (-34 to 60
0
C)
Relay Characteristics:
15 A @ 125 VAC
1/4 HP @ 125/250 VAC NC
10 A @ 277 VAC
1/3 HP @ 125/250 VAC NO
7 A @ 30 VDC
10,000,000 operations
• Inspection and Maintenance
The DCR-1006A requires little maintenance but should be inspection
periodically to ensure proper working order. Ensure that the wire connections
are secure, sealed against the elements and free from corrosion.