DCR-1006A Level Controller
Rev. B2, 7/15
32
Automation Products Group, Inc.
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Relay Trip Types
NEAR
:
Activates whenever the reading is less than the Trip Value.
EXCLSV
(Exclusive):
Activates whenever the reading is less than the Trip Value or greater than the
Trip Value + Trip Window.
H NEAR
(Hysteresis Near):
Activates until the reading exceeds the Trip Value + Trip Window, then
deactivates until the reading falls below the Trip Value.
FAR
:
Activates whenever the reading is greater than the Trip Value.
INCLSV
(Inclusive)
:
Activates whenever the reading falls within the Trip Window.
H FAR
(Hysteresis Far)
:
Activates whenever the reading exceeds the Trip Value + Trip Window, and
remains active until the reading drops below the Trip Value. Once deactivated
the relay will remain inactive until the reading once again exceeds the Trip
Value + Trip Window.
OFF
:
Disables the relay.
LOE
(Loss of Echo)
:
Holds the relay active unless a loss of echo condition (no target detected)
occurs.
INPUT
(Switched Input):
Activates or deactivate the relay based on the state of the switched input
(closed or open).