DCR-1006A Level Controller
Rev. B2, 7/15
16
Automation Products Group, Inc.
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
bASIC
basic
inches, feet, meters
0, 1, 2, 3, 4, 5, 6, 7, 8
ft
3
, Mft
3
, Gallons, m
3
, Liters, in
3
, Barrels
1 to 247
0, 1, 2, 3
DST, LR DST, RS485
6-digit alpha-numeric
UNITS
bACK L
back light
CUSTOM
custom units
VOLUNI
volume units
IN SEL
input select
dECIML
decimal place
SENS N
sensor number
•
bASIC
(Basic Parameters)
UNITS
:
Determines the unit of measure used in all dimensional parameter settings,
including the Maximum Distance, Filter Window, Blanking, and all Application
Type dimensional parameters. The Units setting also determines the unit of
measure for the Calculated Reading when operating in Application Types 1, 2 or
7.
NOTE: the decimal place position for all dimensional parameters remains in a
fixed position based on the Units selected, as shown below:
Meters: 0.000 (3 decimal places)
Feet: 0.00 (2 decimal places)
Inches: 0.0 (1 decimal place)
bACK L
(Back Light):
A
llows the user to adjust the intensity of the display backlight. There are 9 set-
tings from off to 100% intensity.