- Under the “Tools” Menu (A), go to “Com Port” Menu and select the Com Port which is assigned to the
Annunciator (the active Com Port is highlighted in the list).
- Under the “Tools” Menu (A), go to “Baud Rate” menu and select 115200.
- ALCON should be able to communicate with the Annunciator now. To make sure, press the ‘Test’
button (B).
- Under the ‘Window Address’ Menu (C), select the window address (default is 1). Now you can configure
the ‘Logic Sequence’ (D), Input ‘Type’ (E), ‘Alarm Group’ (F) and ‘Auxiliary Relay Function’ (G) for this
window.
- Press the ‘Send the configuration of window’ button (T) and select ‘1’
- Press the ‘‘Send’ button’ (H) to send the new configuration of window ‘1’ to the Annunciator. The window ‘1’
has been configured now. This procedure must be repeated for other windows as well but there is an easier
way to copy the same configuration to other windows as below.
- Press the ‘Copy’ button (J) and select ‘All’
- Press the ‘From Window’ button (K) and select ‘1’
- Press the ‘To Window’ button (L) and select ‘All’
- Press the ‘Copy’ button (M) to copy the new parameters of window ‘1’ to all other windows
- Press the ‘Send the configuration of window’ button (T) and select ‘ALL’
- Press the ‘‘Send’ button’ (H) to send the new configuration to all windows of the Annunciator
Window Parameters setup
- You can also clear the configuration and set it to factory default setting by ‘Clear buttons (P).
- Under ‘File’ menu (R), click on “Save as” to save the new configuration on your computer for future
access.
- To load a saved configuration file, open the file from the ‘File’ menu (R), and send it the Annunciator
- You can also print the new configuration for your records
AIC400 Series Alarm Annunciator
(18)