AH-New
condensing air handling unit
APEN GROUP SPA reserves the right to make changes deemed to be required to its products or documentation
50
code HG0310.05GB ed.A-2010
AH
51
code HG0310.05GB ed.A-2010
AH
TYPE OF GAS G2.350 - Cat. Ls (Only for PL-Poland)
TYPE OF MACHINE
AH034
AH065
(1)
Output
min
max
min
max
CATEGORY
according to the country of destination - see reference
table
SUPPLY PRESSURE
[mbar]
13 [min 10-max 16]
PILOT NOZZLE Ø
[mm]
1 x 0.75
1 x 0.75
GAS CONSUMPTION
(15°C-1013mbar)
[m
3
/h]
1.13
5.17
1.84
9.63
CARBON DIOXIDE -CO
2
CONTENT
[%]
8.4
9
8.4
8.8
FLUE GAS TEMPERATURE
[°C]
31
94
31
86
GAS ORIFICE PLATE
[mm]
Not
required
Not
required
AIR ORIFICE PLATE
[mm]
Not
required
1 x 30.5
(1)
Maximum rated heat input 57.0 kW
NOTE: The minimum and maximum heat outputs of model AH065 are lower with respect to the operation with G20.
Models AH105, AH160, AH210, AH320, AH420 are not suitable for operation with gas G2.350.
The conversion kit for G2.350 is only supplied on request.
TYPE OF GAS G25.1 - Cat. S (Only for HU-Hungary)
TYPE OF MACHINE
AH034
AH065
AH105
(1)
AH160
AH210
(2)
AH320
(3)
AH420
(4)
Output
min
max
min
max
min
max
min
max
min
max
min
max
min
max
CATEGORY
according to the country of destination - see reference table
SUPPLY PRESSURE
[mbar]
25 [min 20-max 33]
PILOT NOZZLE Ø
[mm]
1 x 0.7
1 x 0.7
1 x 0.7
2 x 0.7
2 x 0.7
3 x 0.7
4 x 0.7
GAS CONSUMPTION
(15°C-1013mbar)
[m
3
/h]
0.93
4.29
1.52
7.99
2.21
12.29
2.01
20.2
2.21
24.58
2.21
36.87
2.21
49.16
CARBON DIOXIDE -CO
2
CONTENT
[%]
9.1
9.6
9.3
9.7
9.4
9.6
9.8
10.3
9.4
9.6
9.4
9.6
9.4
9.6
FLUE GAS TEMPERATURE
[°C]
31
94
31
86
28
80
26
70
28
80
28
80
28
80
GAS ORIFICE PLATE
[mm]
1 x 8.9
Not
required
Not
required
Not
required
Not
required
Not
required
Not
required
AIR ORIFICE PLATE
[mm]
Not
required
Not
required
Not
required
Not
required
Not
required
Not
required
Not
required
(1)
Maximum rated heat input 94.0 kW
(2)
Maximum rated heat input 188.0 kW
(3)
Maximum rated heat input 282.0 kW
(4)
Maximum rated heat input 376.0 kW
TYPE OF GAS G27 - Cat. Lw [former GZ41.5] (Only for PL-Poland)
TYPE OF MACHINE
AH034
AH065
(1)
AH105
(2)
AH160
(3)
AH210
(4)
AH320
(5)
AH320
(6)
Output
min
max
min
max
min
max
min
max
min
max
min
max
min
max
CATEGORY
according to the country of destination - see reference table
SUPPLY PRESSURE
[mbar]
20 [min 16-max 23]
PILOT NOZZLE Ø
[mm]
1 x 0.7
1 x 0.7
1 x 0.7
2 x 0.7
2 x 0.7
3 x 0.7
4 x 0.7
GAS CONSUMPTION
(15°C-1013mbar)
[m
3
/h]
0.90
4.15
1.48
7.74
2.50
11.90
1.95
19.52
2.50
23.80
2.50
35.70
2.50
47.60
CARBON DIOXIDE -CO
2
CONTENT
[%]
8.7
9.1
8.6
8.8
8.5
8.7
8.7
9.1
8.5
8.7
8.5
8.7
8.5
8.7
FLUE GAS TEMPERATURE
[°C]
31
94
31
77
28
74
26
67
28
74
28
74
28
74
GAS ORIFICE PLATE
[mm]
1 x 11.4
Not
required
Not
required
Not
required
Not
required
Not
required
Not
required
AIR ORIFICE PLATE
[mm]
Not
required
Not
required
Not
required
1 x 30.5
Not
required
Not
required
Not
required
(1)
Maximum rated heat input 57 kW
(2)
Maximum rated heat input 94 kW
(3)
Maximum rated heat input 150 kW
(4)
Maximum rated heat input 188 kW
(5)
Maximum rated heat input 282 kW
(6)
Maximum rated heat input 376 kW