APEN GROUP SPA reserves the right to make changes deemed to be required to its products or documentation
AH-New
condensing air handling unit
12
code HG0310.05GB ed.A-2010
AH
13
code HG0310.05GB ed.A-2010
AH
ErP table with Variable Air Flow Rates
Model
AH034
AH065
AH105
AH160
AH210
AH320
AH420
PCH module heater efficiency
Seasonal space heating energy efficiency [
Reg.
EU/2281/2016
] [
ƞ
s,h
]*
%
90.4
91.6
91.7
93.2
93.1
93.6
93.8
Emission efficiency [
Reg.EU/2281/2016
] [
ƞ
sflow
]*
%
95.4
95.8
95.5
97.1
97.0
97.5
97.7
Air flow rate
Maximum air flow rate (15°C)
(7)
m
3
/h
3210
6010
9280
15300
18560
27840
37120
Minimum air flow rate (15°C)
(8)
m
3
/h
2247
4207
6496
10710
12992
19488
25984
Model
Capacity
Useful efficiency
Other elements
Consumption of
Power supply
Rated heating capacity
Minimum capacity
Useful
ef
ficiency at
rated
heating capacity
Useful
efficiency
at
minimum
capacity
Casing loss factor
Ignition
burner
consumption
Emissions of nitrogen oxides
Output
efficiency
Seasonal space heat
ing
energy
efficiency
At rated heating capacity
At minimum capacity
In
stand-by
mode
P
rated,h
P
min
ƞ
nom
ƞ
pl
F
env
P
ign
NO
x
ƞ
s,flow
ƞ
s,h
el
max
el
min
el
sb
kW
kW
%
%
%
kW
mg/kWh
ref.GCV
%
%
kW
kW
kW
AH034
33.6
8.1
86.7
96.3
5.0
0.0
46
96.3
91.2
0.074
0.011
0.005
AH065
62.9
13.4
87.2
97.3
5.0
0.0
41
96.6
92.4
0.097
0.015
0.005
AH105
97.2
22.8
87.5
97.6
5.0
0.0
36
96.4
92.5
0.130
0.020
0.005
AH160
160.1
17.8
87.9
97.6
5.0
0.0
28
97.5
93.6
0.246
0.020
0.010
AH210
194.3
22.8
87.5
97.6
5.0
0.0
36
97.4
93.5
0.260
0.020
0.010
AH320
291.5
22.8
87.5
97.6
5.0
0.0
36
97.7
93.8
0.390
0.020
0.015
AH420
388.6
22.8
87.5
97.6
5.0
0.0
36
97.9
94.0
0.520
0.020
0.020
AH160 - R
148.7
17.8
88.1
97.6
5.0
0.0
28
97.6
93.7
0.246
0.020
0.010
AH210 - R
176.8
22.8
88.4
97.6
5.0
0.0
36
97.6
93.8
0.260
0.020
0.010
AH320 - R
265.1
22.8
88.4
97.6
5.0
0.0
36
97.9
94.1
0.390
0.020
0.015
AH420 - R
353.5
22.8
88.4
97.6
5.0
0.0
36
98.1
94.3
0.520
0.020
0.020
NOTES:
*
Symbol in compliance with Reg.EU/2281/2016.
(7)
Reference maximum air flow rate for the calculation of yields and season
energy efficiencies and emissions, with variable air flow rate, listed in the
table. Air flow rate calculated for a ΔT of 30 °C
(8)
Reference minimum air flow rate for the calculation of yields and season
energy efficiencies and emissions, with variable air flow rate, listed in the table.
REGULATION (EU) 2016/2281
Product Information in accordance with Annex 2 point 5 a)
Model:
See table
Warm air heaters B1 [yes/no]:
No
Warm air heaters C2 [yes/no]:
No
Warm air heaters C2 [yes/no]:
No
Type of fuel
[gaseous/liquid/electricity]:
Gaseous
NOTE: The tables above refer to AH air handling units in indoor configuration and installed in the same heated space.
In case of outdoor installation of AH air handling units, or in any case in a place other than the heated space, the
seasonal energy efficiency values must be decreased by 5.0%.