APAR AR653 User Manual Download Page 21

21

 

Table 16.3. Response frame format for the READ

 function (minimum frame length - 7 bytes): 

address of 
the device 

function 4 or 

number of bytes in the 
data field (max. 70*2=140 
bytes) 

data field - register value 

CRC check sum 

1 byte 

1 byte 

1 byte 

÷ 140

 

bytes (HB-LB) 

2 bytes (LB-HB) 

Example 16.3

. Response frame for register value equal to 0: 0x01 - 0x04 - 0x02 - 0x0000 - 0xB930 

Table 16.4. Response frame format for the WRITE

 function (frame length - 8 bytes):   

copy of the claim frame for the WRITE function (Table 16.2) 

Table 16.5. Special answer

 (errors:

 

function field = 0x84 or 0x83 in the case of the READ function and 0x86 in the 

case of the WRITE function): 

Error code 

(HB-LB in the data field)

 

Error description 

0x0001 

non-existing register address 

0x0002 

wrong write register value 

0x0003 

improper function number 

Example 16.5.

 Error frame for a non-existing read register address: 

          0x01 - 0x84 - 0x02 - 0x0001 –0x5130 
 

Table 16.6. Map of registers for the MODBUS-RTU protocol

 

Register 

address  

HEX (DEC)

 

Value  

(HEX or DEC) 

Description of register and access type 

(R- read only register, R/W - read and write register) 

0x00 (0) 

not used or reserved 

0x01 (1) 

653 

device type identifier 

0x02 (2)

 

100 ÷ 999 

controller software (firmware) version 

0x03 ÷ 0x05 

not used or reserved 

0x06 (6) 

0 ÷ 7 

current status of outputs 1, 2, 3: bits 0, 1, 2, bit=1 means the output is 
switched on 

0x07 (7) 

0 ÷ 20,000 

current state of the analog output (0 ÷ 20,000 μA or 0 ÷ 10,000 mV) 

0x08 (8)

 

-100 ÷ 700 

thermocouple cold tip temperature (resolution 0.1

°C  

0x09 ÷ 0x0D 

-1,999 ÷ 19,999 

measured values (input 1, input 2, difference 1-2, sum 1+2, average) 

0x0E ÷ 0x10 

not used or reserved 

Configuration parameters (chapter 10) 

0x11 (17)

 

0 ÷ 5 

parameter 0: 

diS1

 value indicated for the upper display

 

R/W 

0x12 (18)

 

0 ÷ 5 

parameter 1: 

diS2

 value indicated for the lower display

 

R/W 

0x13 (19)

 

20 ÷ 100 

parameter 2: 

briG

 brightness of the display, a 20% increase 

R/W 

Configuration parameters for the measurement channel numbered 

KP

 = 0 ÷ 1 (0=channel 1, 1=channel 2)

 

0x14 (20) +KP*7

 

0 ÷ 16 

parameter 3+KP*7: 

inP

  type of measurement input (chapter 10)

 

R/W 

0x15 (21) +KP*7

 

1 ÷ 10 

parameter 4+KP*7: 

FiL

  digital filtration of measurements (response time)

 

R/W 

0x16 (22) +KP*7

 

0 ÷ 3 

parameter 5+KP*7: 

dot

 position of the point or resolution for temperature

 

R/W 

0x17 (23) +KP*7

 

-1,999 ÷ 18,000 

parameter 6+KP*7: 

Lo

 lower limit or bottom of the indication range

 

R/W 

0x18 (24) +KP*7

 

-1,999 ÷ 18,000 

parameter 7+KP*7: 

Hi

 upper limit or top of the indication range

 

R/W 

0x19 (25) +KP*7 

-500 ÷ 500 

parameter 8+KP*7: 

cAo

 zero offset for measurements 

R/W 

0x1A (26) +KP*7 

850 ÷ 1,150 

parameter 9+KP*7: 

cAG

 calibration of inclination (sensitivity) for 

measurements 

R/W 

Summary of Contents for AR653

Page 1: ...AR653 AR663 UNIVERSAL TWO CHANNEL CONTROLLERS Version 1 1 5 2016 02 24 APAR SALES OFFICE 05 090 Raszyn ul Ga czy skiego 6 Poland Tel 48 22 101 27 31 48 22 853 49 30 E mail automatyka apar pl Website...

Page 2: ...7 9 1 FUNCTION BUTTON 8 10 SETTING OF THE CONFIGURATION PARAMETERS 9 11 QUICKACCESS MENU 13 12 OUTPUT OPERATION CONFIGURATION 13 12 1 CHANGING THE OUTPUTS SET VALUES 13 12 2 TYPES OF OUTPUT CHARACTER...

Page 3: ...pulse disturbances ground or zero metal rails on which rail mounted devices are installed Make sure to remove the protective film from the LED display before the first use of the device 3 GENERAL CHAR...

Page 4: ...e copying of configuration AR653 panel enclosure IP65 on the front AR663 enclosure for the DIN35 rail IP20 options to be selected in the ordering method 24 V AC DC power supply SSR control outputs 0 2...

Page 5: ...te outputs 3 transmitter or SSR relay P1 P2 P3 standard 8A 250V for resistance loads 1 main SPDT 2 additional SPST NO SSR SSR1 SSR2 SSR3 option transistor type NPN OC 11 V internal resistance 440 Anal...

Page 6: ...scription of terminal strips Terminals Description IN1 IN2 IN3 input Pt100 Ni100 Pt500 Pt1000 resistance 2 and 3 wire IN2 IN3 thermocouple input TC J K S B R T E N and voltage input 0 60 mV IN3 GND 9...

Page 7: ...easiest method is connecting a suitable suppression module directly to the inductive load terminals Generally a suitable type of suppression system should be selected for each inductive load Modern co...

Page 8: ...OWN after hold time 0 5 s c functions of the LED signaling diodes Diode marking Description 1 2 3 signals switching on of outputs P1 SSR1 P2 SSR2 and P3 SSR3 9 1 FUNCTION BUTTON The F function button...

Page 9: ...pressing the SET button or cancel it by pressing the F or UP and DOWN buttons the latter two must be briefly pressed simultaneously by pressing the UP and DOWN buttons or the F button again you will...

Page 10: ...oelectric sensor thermocouple type S 40 1 600 C tc b thermoelectric sensor thermocouple type B 300 1 800 C tc r thermoelectric sensor thermocouple type R 40 1 600 C tc t thermoelectric sensor thermoco...

Page 11: ...rementsensor signal noCh no change oFF switched off on switched on hAnd manual mode withsetoutputsignal level parameter26 HSEt chapter12 8 noCh 24 Fun2 function of output 2 chapter 12 2 oFF off hAnd m...

Page 12: ...units min 2 0 1 C 45 th1 time of stage 2 0 8640 min duration of stage Pr 2 0 maintains stage Pr 2 permanently 30 min 46 th1 time of stage 4 0 8640 min duration of stage Pr 4 0 maintains stage Pr 4 per...

Page 13: ...ameter 29 Fun3 oFF or hAnd t St start stop of PID tuning chapter 12 5 optional element unavailable when parameter 37 tunE oFF P St start stop of the process controller chapter 12 7 optional element un...

Page 14: ...l is determined by parameter 33 AtYP chapter 10 Table 10 The analog output can work in one of the following modes retransmission of measurement parameter 34 outA rEtr manual mode 34 outA hAnd and as a...

Page 15: ...ntrolled object e g a furnace In order to simplify the operation the controller is provided with the advanced PID parameter selection functions described in chapter 12 5 Also it is always possible to...

Page 16: ...arameter selection method depends on the nature of the initial conditions In the case of a stabilized controlled value the run up quick method will be selected in other cases the oscillation method sl...

Page 17: ...rrelation between those parameters only one parameter should be changed and the impact of the change on the process should be observed a oscillations about the threshold increase the range of proporti...

Page 18: ...Also the outputs can be configured for quick unconditional manual mode controlled by the F function button by programming as appropriate parameter 50 Func chapter 9 1 measurement error of the sensor r...

Page 19: ...rter require installation of the supplied serial portdrivers on the computer Communicationwith devices is effected using a protocol compatible with MODBUS RTU chapter 16 The following applications are...

Page 20: ...rs USB may have integrated polarizing and terminating resistors in such a case there is no need to use external elements During configuration of the network make sure to observe the cable installation...

Page 21: ...ion R 0x03 0x05 0 not used or reserved R 0x06 6 0 7 current status of outputs 1 2 3 bits 0 1 2 bit 1 means the output is switched on R 0x07 7 0 20 000 current state of the analog output 0 20 000 Aor 0...

Page 22: ...er 34 FunA function of analog output R W 0x34 52 1 999 18 000 parameter 35 A Lo lower indication for retransmission R W 0x35 53 1 999 18 000 parameter 36 A Hi upper indication for retransmission R W 0...

Page 23: ...1 0100 10 120 TCN4L 22R TX4H 14R TX4H 24R TX4H A4R TX4H B4R TX4L 14R TX4L A4R TX4L B4R TX4M 14R TX4M 24R TX4M A4R TX4M B4R QP99 CP 02 CP82 CP99 R38 LAOO R38 LARR 72 11304023 0150 0050 72 11304027 0150...

Reviews: