Notes: (1)
– for
FiL
=
1
the response time is equal to 0.5 s, for
FiL
=
20
it is equal to at least 4 s. Higher degree of
filtration means a "smoother" measured value and a longer response time, which is recommended in
the case turbulent measurements (e.g. water temperature in the boiler).
(2)
– applies to analog inputs ( mA, V, mV, Ω )
(3)
– the parameter also defines the state of the output outside of the measurement range
11. QUICK ACCESS MENU
In the measurement mode (when the measured value is displayed), it is possible to immediately access certain
configuration parameters and functions without the need to enter a password. This possibility is offered by the
quick menu, which can be accessed by pressing the
[SET]
button. The parameter is selected and edited in the
same way as described above (in chapter 10).
Table 11. List of elements accessible in the quick configuration menu.
Element
Description
SEt1
set value 1 (parameter 20:
SEt1
), optional element - unavailable when parameter 19:
out1
=
hAnd
, changes
blocked during selection of parameters (tuning) of the PID (
chapter 12.5)
and in the process control mode
(
chapter 12.7)
and the mode of change of the set value 1 to
SET3
(
chapter 9.1)
SEt2
set value 2 (25:
SEt2
), optional element - unavailable when parameter 24:
Fun2
=
oFF
or
hAnd
SEt3
set value 3 (30:
SEt2
), optional element - unavailable when parameter 29:
Fun3
=
oFF
or
hAnd
t-St
start/stop of PID tuning (
chapter 12.5)
, optional element - unavailable when parameter 37:
tunE
=
oFF
P-St
start/stop of the process controller (
chapter 12.7)
,
optional element - unavailable when parameter 43:
rAMP
=
oFF
HSEt
set value of the manual mode (42:
HSEt
),
optional element - available for outputs in the manual operation mode
12. OUTPUT OPERATION CONFIGURATION
The programmable architecture of the controller enables using it in many fields and applications. Before the
operation of the device starts, it is necessary to set the parameters according to specific requirements (chapter 10).
A detailed description of configuration of the operation of outputs is given in chapters 12.1÷ 12.8. The default
(factory) configuration is the following: outputs 1 is related to input 2 and output 2 is related to input 2, control
mode ON/OFF with hysteresis, output 3 and the analog outputs are switched off (Table 10,
Factory settings
column).
12.1. CHANGING THE OUTPUTS SET VALUES
The simplest way to change the set value for output 1 (parameter 20:
SEt1
or 42:
HSEt
when output 1 is in the
manual mode) is to use the
[UP]
button or the
[DOWN]
button. In the case of the other outputs, the quick menu
can be used (chapter 11). As an alternative, it is possible to change the set value in the parameter configuration
mode (using the methods described in chapter 10).
12.2. TYPES OF OUTPUT CHARACTERISTICS
The mode of operation of each output is programmed using parameters 19:
Fun1
, 24:
Fun2
, and 29:
Fun3
, chapter
10, Table 10.