Ozone Monitor, Temperature and Humidity

Modbus, Analog, Relay Outputs

4

db_ozone_wall_duct_ap_uk

O3

Parameter Setup

Power off and remove the front cover. There is a set of 4 dip switches on the upper left corner on the circuit board.

DIP 1

OFF - Volume concentration

ON - Mass concentration

Leaving factory (default): OFF

DIP 2

OFF - Celcius

ON - Fahrenheit

Leaving factory: OFF

DIP 3

OFF - Relay 1 control valid at the first setpoint

ON - Relay 1 control valid at the second setppoint

Leaving factory: OFF

DIP 4

OFF - Relay 2 control valid at the first setpoint

ON - Relay 2 control valid at the second setpoint

J1: connected (short circuit) - analog start value at 2V/4mA; disconnected - analog start value at 0V/mA

J2: connected - test of analog output bottom limit; disconnected - analog output works normally

J3: connected - test of analog output upper limit; relay outputs, backlights & buzzer alarm; disconnected - everything works normally

J4: connected - zero point calibration

After using the ozone sensor for more than one year, the sensor needs to be calibrated again. Put the monitor into the space zero ozone 

(make sure the ozone level in the space is zero). 

Connect the jumper first and then disconnect the jumper when the buzzer stops alarming (about 30 seconds). 

The ozone level at this time will be 0ppm.

J5: connected - single point calibration.

Connect the jumper first and then disconnect the jumper when the buzzer stops alarming (about 30 seconds). 

The ozone level at this time will be the value showed in parameter 26.

Parameter Setup:

1.  Parameters can be set through RS485 OR

2.  Connect 

J1 & J2

 at the same, DIP 1 & 2 to ON. 

 

Parameters can be set through infrared remote controller  

(           keys to adjust values,  

MODE

 key to switch items)