Sep. 18

Automatikprodukter

Ozone Monitor, Temperature and Humidity

Modbus, Analog, Relay Outputs

5

db_ozone_wall_duct_ap_uk

O3

LCD Display

Parameter

Setting Range

Default

-01

Temperature differential value

±3.0

O

C/±6

O

F

0

-02

Manual humidity calibration

5~99%rH

50

-03

Real-time ozone value 

calibration

0~ upper limit of measuring 

range as 16ppm 

e.g. if set this value at 16 

through RS485 or remote con-

troller, the sensor will take the 

present ozone level"

0

-04

First setpoint of relay 1

1~ upper limit of measuring 

range

1000

-05

Second setpoint of relay 1

1~ upper limit of measuring 

range

2000

-06

First setpoint of relay 2

1~ upper limit of measuring 

range

3000

-07

Second setpoint of relay 2

1~ upper limit of measuring 

range

4000

-08

Relay differential value

1~1000

100

-09

Relay control mode

0: to increase ozone concen

-

tration 1: to decrease ozone 

concentration

1

-10

Demarcation point between green 

backlight and yellow backlight

1~ upper limit of measuring 

range

1500

-11

Demarcation point between yellow 

backlight and red backlight

1~ upper limit of measuring 

range

3500

-12

Buzzer alarm

0: invalid                       1: valid

1

-13

Alarm setpoint

1~ upper limit of measuring 

range

3500

-14

Alarm differential value

1~1000

100

-15

Alarm song album

0: Tick-tick

 

1: Music-For Elise

 

2: Music-Mariage d`amour"

0

-16

Sensor warm-up time

1~ 600 seconds

120

-17

Display in ppm or ppb

1: ppm         2: ppb

2

-18

RS485 communication address

1~ 255

1

-19

RS485 Baud rate 

1: 4800bps 2: 9600bps 3: 

14400bps 

4

-20

RS485 Parity bits and Stop bits 

selectable 

1: None 1Stop; 2: None 2Stop

 

3: Odd 1 Stop   4:Even 1 Stop

1

-21

Sensor detection upper limit value 

1~ upper limit of measuring 

range 

5000

-22

Self calibration 

0: invalid 1: valid 

1

-23

Manual zero point calibration avail

-

able 

Adjust the setpoint from 0 to 

1, the present ozone level is 

deemed as 0ppm 

0

-24

Manual single point calibration 

available 

Adjust the setpoint from 0 to 

1, the present ozone level is 

deemed as the value in -26 

0

-25

Manual vernier regulation of detec

-

tion value ( AD value calibration ) 

-9999~ 9999 

-- 

Modbus Register