Appendix A: Configuration Examples
28 (38)
A.2
PROFINET networking via Bluetooth
®
Configuration with Easy Config
Fig. 18
PROFINET wireless network
This example describes how to connect a PROFINET IO device and a PROFINET PLC over
Bluetooth using two Wireless Bridges and Easy Config.
The Wireless Bridges will be configured with PROFINET optimization, which means that
PROFINET messages will have priority over TCP/IP frames.
See the respective documentation for the IO device and PLC on how to configure them for
PROFINET communication.
Configuration
1.
Reset both Wireless Bridges to the factory default settings.
2.
Connect Wireless Bridge 1 to the IO device and Wireless Bridge 2 to the PLC.
3.
Set Wireless Bridge 1 to Easy Config
Mode 4
.
This unit will now be discoverable and open for automatic configuration.
4.
Set Wireless Bridge 2 to Easy Config
Mode 8
This unit should now automatically discover and configure unit 1 as a Bluetooth client, and
configure itself as an access point. Both units will be optimized for PROFINET.
The IO device should now be able to communicate with the PLC as if using a wired connection.
Adding More Devices
Up to 6 additional clients can be added by repeating the procedure. Each new client will be
assigned the next free IP address within the current subnet.
The IO cycle update time for each IO device must be set to ≥ 64 ms.