Anybus Configuration Manager (MAPS)
26 (56)
Trend Logs
In this section, all trend logs related configuration can be carried out. Up to 5 Trend Logs can be
created.
Fig. 23
Trend Logs
Name
Descriptive name for the trend log
Trend Log Instance
BACnet Object Instance for the trend log
Trend Mode
Select the type of trend mode to use:
•
Polled
: The poll cadence for this needs to be set in the Interval parameter.
•
COV
: The COV increment to be considered needs to be set in the COV
Increment parameter.
•
Triggered
: The trend log will be triggered by the BACnet BMS system.
Interval
Applicable only if Trend Mode = Polled.
COV Increment
Applicable only if Trend Mode = COV.
Properties
Additional properties can be defined:
•
Enable
: It allows enabling or disabling the specific Trend Log even if the
Trend Log is in the valid time range.
•
Stop Buffer Full
: If enabled, it will stop the Trend Log when the buffer is full.
If disabled, it will roll up the Trend Log information keeping the last 2880 valid
values.
Date Configuration
Set the period when Trend Logs will be active. It can be set as always or in a time
frame or range
Selected Objects
Selection of objects to be included inside a Trend Log. Up to 10 different BACnet
Objects can be selected.