Appendix C: BACnet Objects
45 (56)
Device Object Type (continued)
Property Identifier
Property Datatype
Value
ASHRAE
Anybus
Align_Intervals
BOOLEAN
-
O
-
Interval_Offset
Unsigned
-
O
-
Profile_Name
CharacterString
-
O
-
* Only available when MSTP is used ** Configurable through the configuration tool
Analog Input Object Type
Property Identifier
Property Datatype
Value
ASHRAE
Anybus
Object_Identifier
BACnetObjectIdentifier
(Analog Input, 0)
R
R
Object_Name
CharacterString
Configurable through BACnet
and Config Tool
R
R
Object_Type
BACnetObjectType
ANALOG_INPUT (0)
R
R
Present_Value
REAL
x
R
R
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE/TRUE, FALSE,
FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0),
UNRELIABLE_OTHER (7)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Update_Interval
Unsigned
-
O
-
Units
BACnetEngineeringUnits
Configurable through BACnet
and Config Tool
R
R
Min_Pres_Value
REAL
-
O
-
Max_Pres_Value
REAL
-
O
-
Resolution
REAL
-
O
-
COV_Increment
REAL
0
O
R
Time_Delay
Unsigned
-
O
R*
Notification_Class
Unsigned
-
O
R*
High_Limit
REAL
-
O
R*
Low_Limit
REAL
-
O
R*
Deadband
REAL
-
O
R*
Limit_Enable
BACnetLimitEnable
-
O
R*
Event_Enable
BACnetEventTransitionBits
-
O
R*
Acked_Transitions
BACnetEventTransitionBits
-
O
R*
Notify_Type
BACnetNotifyType
-
O
R*
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
-
O
R*
Profile_Name
CharacterString
-
O
-
* Only available when specific object has a Notification Class configured
Analog Output Object Type
Property Identifier
Property Datatype
Value
ASHRAE
Anybus
Object_Identifier
BACnetObjectIdentifier
(Analog Output, 0)
R
R
Object_Name
CharacterString
Configurable through BACnet
and Config Tool
R
R
Object_Type
BACnetObjectType
ANALOG_OUTPUT (1)
R
R
Present_Value
REAL
x
W
W
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Modbus to BACnet Gateway User Manual
SCM-1202-049 1.0