Doc.Id. SCM-1200-093
Anybus Communicator for Modbus Plus
Doc.Rev. 3.01
Appendix C
C. Troubleshooting
Problem
Solution
Problem during configuration Upload / Download.
The Config Line “LED” turns red in the Anybus Configura-
tion Manager.
•
Serial communication failed. Try again
The serial port seems to be available, but it is not possible
to connect to the gateway
•
The serial port may be in use by another application.
Exit the Anybus Configuration Manager and close all
other applications including the ones in the system
tray.
Try again
•
Select another serial port
Try again
Poor performance
•
Right click ‘subnetwork’ in the Navigation window and
select ‘subnetwork Status’ to see status / diagnostic
information about the subnetwork.
If the gateway reports very many retransmissions,
check your cabling and/or try a lower baud rate setting
for the subnetwork (if possible).
•
Is the Subnet Monitor in the Anybus Configuration
Manager active?
The subnetwork monitor has a negative influence on
the overall performance of the gateway, and should
only be used when necessary.
•
Is the Node Monitor in the Anybus Configuration Man-
ager active?
The node monitor has a negative influence on the
overall performance of the gateway, and should only
be used when necessary.
No subnetwork functionality
•
Use the ‘Data logger’-functionality to record the serial
data communication on the subnetwork.
•
If no data is being transmitted, check the configuration
in Anybus Configuration Manager.
•
If no data is received, check the subnetwork cables.
Also verify that the transmitted data is correct.