background image

Antti-Teollisuus Oy 

408099 

11-2020

Blower units and axial blowers

SPARE PARTS DRAWING 5,5 kW

Part

Item

Denomination

Drawing No.

Pcs. Weight

1

A72982

BLOWER CHAMBER RIGHT LG 5.5kW/7.5kW M10

A72982-0

1

88,16

2

A72458

SUCTION CONE LG 5.5 kW M09

A72458-A

1

6

3

A72463

ROTOR LG 5.5 kW M10

A72463-A

1

31,38

4

504591

AIR DUCT BAND D625

A71000-0

1

0,52

5

303545

MOTOR 5.5Kw 1500r B3

-

1

43,00

6

400340

WASHER ZN DIN440 D 58/18x5 045918

0

1

0,09

7

112320

SERRATED WASHER M12

0

5

0,002

8

102573

HEX BOLT M12x50 DIN931    

0

1

0

9

102550

HEX BOLT ZN12x45 DIN933    

0

4

0,01

10

111560

WASHER ZN M12 ZN DIN 125

0

4

0

11

110570

NUT M12 DIN934

0

4

0

12

104243

SOCKET SCREW M6X70 AM

0

1

0,02

13

110530

NUT M6 DIN 934

0

1

0

SPARE PARTS DRAWING 7.5 kW

Part

Item

Denomination

Dwg. no.

Pcs. Weight

1

A72982

BLOWER CHAMBER RIGHT LG 5.5kW/7.5kW M10

A72982

1

88,16

2

A72410

SUCTION CONE LG 7.5kW M10

A72410

1

4,59

3

402016

ROTOR M84 A330 NORM

1543

1

35,18

4

504591

AIR DUCT BAND D625

A71000

1

0,52

5

303550

MOTOR 7.5Kw 1500r B3

1

48,50

6

400340

WASHER ZN DIN440 D 58/18x5 045918

1

0,09

7

102573

HEX BOLT M12x50 DIN931    

1

0

8

104243

SOCKET SCREW M6X70 AM

1

0,02

9

110530

NUT M6 DIN 934

1

0

10

102550

HEX BOLT ZN12x45 DIN933    

4

0,01

11

111560

WASHER ZN M12 ZN DIN 125

5

0

12

112320

SERRATED WASHER M12

5

0,002

Summary of Contents for 408099

Page 1: ...antti fi Installation and Operating Instructions RADIAL BLOWER UNITS 5 5 kW 7 5 kW 11kW 15 kW AND AXIAL BLOWERS 408099 en 11 2020 You ll see the difference ...

Page 2: ... 5 kW AND 7 5 kW 7 DIMENSION AND DELIVERY CONTENTS DRAWING 11 kW AND 15 kW 9 CHANGING HANDEDNESS OF THE 5 5 kW AND 7 5 kW BLOWER MODELS 11 PRESENTATION OF 17 2 kW and 8 66 kW AXIAL BLOWERS 13 114552 AXIAL BLOVER 1 STAGE 17 2kW ø710mm 108kg 14 114554 AXIAL BLOVER 1 STAGE 8 66kW ø710mm 75kg 14 SERVICING 20 ELECTRIC INSTALLATION FIRE THERMOSTAT 20 GUARANTEE 21 EU Declaration of Conformity 22 CONTENTS...

Page 3: ... with both left handed and standard handedness with pipe outlets of either D630 or D800 see the table below presenting our number for the item and further down the handedness If the pipeline is long or there are several elbows we recommend pipe size D800 for the 15 kW blower units This way it is possible to prevent unreasonably high pressure loss in the pipe Weight A72835 blower unit 5 5 kW right ...

Page 4: ...x45 DIN933 0 4 0 01 10 111560 WASHER ZN M12 ZN DIN 125 0 4 0 11 110570 NUT M12 DIN934 0 4 0 12 104243 SOCKET SCREW M6X70 AM 0 1 0 02 13 110530 NUT M6 DIN 934 0 1 0 SPARE PARTS DRAWING 7 5 kW Part Item Denomination Dwg no Pcs Weight 1 A72982 BLOWER CHAMBER RIGHT LG 5 5kW 7 5kW M10 A72982 1 88 16 2 A72410 SUCTION CONE LG 7 5kW M10 A72410 1 4 59 3 402016 ROTOR M84 A330 NORM 1543 1 35 18 4 504591 AIR ...

Page 5: ... 41560 0 2 0 46 10 117911 PLATE STICKER 25x50 THT 17 434 3 0 1 0 00 11 400342 WASHER PL5 D 52 13 0 4 0 08 12 102573 HEX BOLT M12x50 DIN931 0 4 0 00 13 111560 WASHER ZN M12 ZN DIN 125 0 4 0 00 14 112320 LOCK WASHER M12 112320 DIN 6798A 0 4 0 00 15 110570 NUT M12 DIN934 0 4 0 00 16 101860 HEX BOLT ZN 8x35 DIN933 0 4 0 00 17 110540 NUT M8 DIN 934 0 120 0 00 18 117774 PLATE STICKER DANGER FROM ABOVE 0...

Page 6: ...E STICKER 25x50 THT 17 434 3 0 1 0 00 11 400342 WASHER PL5 D 52 13 0 4 0 08 12 102573 HEX BOLT M12x50 DIN931 0 4 0 00 13 111560 WASHER ZN M12 ZN DIN 125 0 4 0 00 14 112320 LOCK WASHER M12 112320 DIN 6798A 0 4 0 00 15 110570 NUT M12 DIN934 0 4 0 00 16 101860 HEX BOLT ZN 8x35 DIN933 0 4 0 00 17 110540 NUT M8 DIN 934 0 120 0 00 18 117774 PLATE STICKER DANGER FROM ABOVE 0 2 0 00 19 400340 WASHER PL5 D...

Page 7: ...CONVERSION PART BLOWER D630 22430 1 10 6 2 504591 AIR DUCT BAND D625 A71000 3 0 55 3 32796 AIR PIPE D625 223 FLEXIBLE PART 32796 2 3 5 4 32452 AIR PIPE ADJ PLATE D625 617 230 SOLID 32452 1 10 7 5 A72459 BLOWER INTERM PLATE LONG LG 5 5kW 7 5kW M10 A72459 2 1 6 A72462 BLOWER INTERM PLATE SHORT LG 5 5kW 7 5kW M10 A72462 2 0 2 DIMENSION AND DELIVERY CONTENTS DRAWING 5 5 kW AND 7 5 kW ...

Page 8: ...0 8000 12000 16000 20000 0 500 1000 1500 2000 Vastapaine Pa Ilmamäärä m h Antti keskipakopuhallin 7 5 kW 0 5000 10000 15000 20000 25000 0 500 1000 1500 2000 Vastapaine Pa Ilmamäärä m Air amount m h Counter pressure Pa Antti Radial Blower 5 5 kW Antti Radial Blower 7 5 kW Counter pressure Pa Air amount m h ...

Page 9: ...ight 1 22474 CONVERSION PART BLOWER D800 22474 1 13 4 2 504591 AIR DUCT BAND D625 A71000 1 0 55 3 22440 AIR PIPE D800 280 FLEXIBLE PART 22440 2 4 5 4 22478 AIR PIPE ADJ PLATE D800 350 SOLID 22478 1 17 5 5 508418 ADAPTER FOR AIR DUCT D630 800 A J 31904 1 5 5 DIMENSION AND DELIVERY CONTENTS DRAWING 11 kW AND 15 kW BLOWER UNIT 15 kW STANDARD ...

Page 10: ...000 20000 25000 30000 0 500 1000 1500 2000 2500 Vastapaine Pa Ilmamäärä m h Antti keskipakopuhallin 15 kW 0 5000 10000 15000 20000 25000 30000 0 500 1000 1500 2000 2500 Vastapaine Pa Ilmamäärä m Counter pressure Pa Air amount m h Air amount m h Counter pressure Pa Antti Radial Blower 11 kW Antti Radial Blower 15 kW ...

Page 11: ...r to make the legs easier to remove and prevent the blower from breaking Fig 2 Remove the legs from the blower chamber 2 Fig 3 Fix the legs on the other side of the blower chamber as illustrated Fix the bolts carefully and wrench them tight It is vital that also the fixing bolts for the side supports are put back in place en largement in Fig 4 3 Fig 4 You can lift the blower upright as soon as the...

Page 12: ...his prevents possible vibrations from passing on to the piping or heavy loads created in the piping from passing on to the blower unit So the piping must be supported and the flexible part must not be subjected to any excess load resulting from the weight of the piping INSTALLATION The blower unit is heavy and because of possible vibrations resulting from its unbalance it must be placed on a firm ...

Page 13: ...otors are by one size smaller than stated in the nameplate but the given output however is correct Run ning at a greater load is possible provided that the cooling effect is sufficient The delivery of the axial blower includes a suction bell to be installed as shown in the drawing taking note of the installation practice applied Also a fire thermostat is delivered with the blower There are install...

Page 14: ...0Hz 35Hz 30Hz 0 5000 10000 15000 20000 25000 30000 35000 40000 45000 0 200 400 600 800 1000 1200 1400 Ilmamäärä m h Vastapaine Pa Aksiaalipuhallin 17 2 kW 50Hz 45Hz 40Hz 35Hz 30Hz 0 5000 10000 15000 20000 25000 30000 0 200 400 600 800 1000 1200 1400 1600 Ilmamäärä m h Vastapaine Pa Aksiaalipuhallin 8 66 kW Air amount m h Counter pressure Pa Counter pressure Pa Air amount m h ...

Page 15: ...Antti Teollisuus Oy 15 408099 11 2020 Blower units and axial blowers Note Suction bell A75893 ...

Page 16: ...Antti Teollisuus Oy 16 408099 11 2020 Blower units and axial blowers SUPPORT FAN BACKDRAFT DAMPER SILENCER INSTALLATION PARTS ...

Page 17: ...ng the direction of rotation is punched in the impeller blades The fire thermostat and the outlet temperature sensor shall be installed in their designated installation points as shown in the adjacent drawings Installation of the temperature transmitter installation of the tire thermostat Check the direction of rotation of the dryer heater fan and the direction of airflow before start up Direction...

Page 18: ...izontally the temperature transmitter should be installed in the blower located in the middle Each blower unit shall be equipped with a fire thermostat and if there is more than just one blower the contacts of the thermostats shall be connected in series 17 2 kW 50 Hz 104 dB 45 Hz 103 dB 40 Hz 98 dB 8 66 kW 50 Hz 103 dB 45 Hz 93 dB 40 Hz 90 dB Sound pressure emitted by the blowers at a counter pre...

Page 19: ...tti Teollisuus Oy 19 408099 11 2020 Blower units and axial blowers Principle drawing presenting installation in the air channel end of the dryer A76263 AIR CHANNEL AXIAL 0 5m A76264 AIR CHANNEL AXIAL 1 0m ...

Page 20: ...ryer immediately after the pre set temperature has been reached for example as a result of fire inside the dryer The fire thermostat is delivered with the blowers A fire thermostat is installed in every outlet pipe from the blower Normally the thermostat is adjusted to 60 C The ther mostat comes with a 2 metre long capillary pipe which makes it possible to install the thermostat box in a location ...

Page 21: ...espective manufacturers apply A prerequisite for validity of the guarantee is that the instructions issued by the manufacturer and the valid regula tions have been followed during installation use and service of the blowers A prerequisite for validity of the product guarantee is that the control system and the components used are ap proved by Antti Teollisuus All matters related to the guarantee s...

Page 22: ...eclaration of Conformity ANTTI TEOLLISUUS OY Koskentie 89 FI 25340 KANUNKI Tel 358 2 7744700 declares that BLOWER UNITS AND AXIAL BLOWERS conform with the provisions of the following directives Machine Directive 2006 42 EU Kuusjoki 02 01 2020 Kalle Isotalo Managing Director ...

Page 23: ......

Reviews: