![Ansul INERGEN 150-BAR Manual Download Page 19](http://html1.mh-extra.com/html/ansul/inergen-150-bar/inergen-150-bar_manual_2946345019.webp)
Description
Electrical actuation of an agent cylinder and/or selector
valves is accomplished by an HF electric actuator interfaced
through an AUTOPULSE Control System. This actuator can
be used in hazardous environments where the ambient tem-
perature range is between 0 °F to 130 °F (–18 °C to 54 °C).
The HF electric actuator meets the requirements of N.E.C.
Class I, Div. 1, Groups B, C, D and Class II, Div. 1, Groups
E, F, G. A maximum of two HF electric actuators can be
used on a single AUTOPULSE release circuit. When utiliz-
ing only one HF electric actuator, an in-line resistor, Part No.
73606, is required in the supervised release circuit.
The actuator specifications are:
Nominal
Rated Voltage
Voltage
Minimum Maximum
12 VDC @ 0.57 amps
12.0 VDC
14.0 VDC
In auxiliary or override applications, a manual-local override
valve actuator or a manual cable pull actuator can be
installed on top of the HF electric actuator by removing the
safety cap.
A reset tool is required to reset the actuator after operation.
The actuator contains a standard 1/2 in. threaded female
straight connector for electrical conduit hookup.
Shipping Assembly
Part No.
Description
73327
HF electric actuator
75433
HF Reset Tool
Thread
Component
Material
Size/Type
Approvals
HF Electric
Body:
1/2 in.
UL (EX-4510);
Actuator
Brass
Straight
Listed for use
Plunger:
Female
with FM
Stainless
Approved
Steel
systems
4 1/2 IN.
(11.4 cm)
2 1/4 IN.
(5.7 cm)
001395
006037
Ø 2.50
3.025
1 1/4 – 18 UNEF
1 1/8 – 18 UNEF
Description
The Booster Actuator, Part No.
428949, is used when electric actua-
tion is required on the selector valve
or the CV-98 cylinder valve. The
actuator mounts directly to the com-
ponent and then a HF electric actua-
tor mounts to the top of the booster
actuator.
The Booster Actuator requires reset-
ting after actuation. A Reset Tool,
Part No. 429847, is available for this
use.
System Components
UL EX-4510 2-1-12 Page 1-3.4
REV. 3
Valve Electric Actuation
ANSUL
®
1 1/4 – 18
Copyright © 2012 Tyco Fire Products LP.
All rights reserved.
Form No. F-99025-03
One Stanton Street
+1-715-735-7411
Marinette, WI 54143-2542
www.ansul.com
Summary of Contents for INERGEN 150-BAR
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 12: ......
Page 14: ......
Page 16: ......
Page 20: ......
Page 22: ......
Page 24: ......
Page 26: ......
Page 28: ......
Page 30: ......
Page 32: ......
Page 36: ......
Page 44: ......
Page 46: ......
Page 50: ......
Page 52: ......
Page 54: ......
Page 56: ......
Page 60: ......
Page 62: ......
Page 64: ......
Page 66: ......
Page 68: ......
Page 72: ......
Page 74: ......
Page 76: ......
Page 78: ......
Page 80: ......
Page 82: ......
Page 84: ......
Page 86: ......
Page 88: ......
Page 90: ......
Page 92: ......