SECTION 6 – TEST AND PLACE IN SERVICE
2014-APR-30 REV. 0 PAGE 6-17
CHECKFIRE 110
Detection and Actuation System
TABLE 6-7: PLACING CHECKFIRE 110 CONTROL mODULE IN SERVICE (Continued)
6. Remove actuator cap on top of Electric-Pneumatic Actua-
tor and retain for future use.
Before installing PAD(s) place control module in
Isolate mode, see Table 2 – Isolate mode.
CAUTION
!
When handling the PAD, always point actuating end
away from yourself and others. On electrical initiation,
PAD operates very quickly and a small brass disk force-
fully separates from actuating end. Physical injury may
occur from contact with the actuating pin and/or the
detaching disk.
7. Write installation date on PAD, DO NOT cover manufac-
turing date on label. Install PAD into Release Circuit Drop
Cable. Verify o-ring is in place on PAD.
NOTICE
The PAD (Protracting Actuation Device)
must be replaced after being in-service for
five years.
a. The in-service date should be recorded in
installation and maintenance records and
written on the PAD label with permanent
marker at the time of installation.
b. The PAD has a 10 year shelf life when
stored in an environmentally stable loca-
tion. The 5 year in-service life may not
extend beyond the 10 year shelf life. (The
month and year of manufacture is printed
on the label located on the PAD body).
Install all PADs in the Release Circuit Drop Cable(s) then
confirm all faults are cleared prior to installing Release
Circuit Drop Cable(s) to actuator(s).
8. Attach Release Circuit Drop Cable to Electric-Pneumatic
Actuator, hand-tighten connector. (Keep actuator cap for
recharge and maintenance procedures.)
NOTICE
Be sure the control module does not have
any faults or alarms before installing Release
Circuit Drop Cable to Electric-Pneumatic
Actuator.
Continues Next Page
009171
CAUTION
FOR ELECTRIC ACTuATION
ONLY 1/4 IN. BRASS PLuGS
MuST REMAIN IN PLACE OR
FIRE SuPPRESSION SYSTEM
WILL NOT OPERATE.
009169
WRITE INSTALL DATE ON
PAD LABEL
MAKE SuRE
MANuFACTuRING DATE
IS READABLE
009170
VERIFY O-RING
ON PAD
PAD FIELD INSTALLED IN CABLE
009168
REMOVE
ACTuATOR CAP
AND KEEP