SECTION 6 – TEST AND PLACE IN SERVICE
PAGE 6-10 REV. 0 2014-APR-30
CHECKFIRE 110
Detection and Actuation System
TABLE 6-4: OPERATIONAL TEST (Continued)
Detection Circuit: Test Time Delay Restart
1. Reset DCT to normal position.
2. Reset RCT - press reset button.
3. Reset control module to Normal: Press and hold the
“DELAY/Reset/Silence” button for 3 seconds; Power LED
and Sounder quickly pulse 3 or 5 times, then Power LED
remains GREEN steady-on.
4. Initiate alarm condition by turning DCT switch to ALARM.
5. Before time delay period expires (5 or 15 seconds), push
“DELAY/Reset/Silence” button to restart time delay (3 or
5 pulses indicate time is reset). Time delay resets to full
delay period. (Time delay reset may be repeated multiple
times. Press and release.)
Note: Holding button down does not pause time delay.
6. Allow Control Module to complete time delay cycle then
during Release Activated (“PuSH to Activate / Alarm
When Lit” RED LED and Sounder remain steady-on for
10 seconds) push the “DELAY/Reset/Silence” button.
Verify:
a. Time delay will not restart.
b. Sounder will not silence.
7. Confirm successful release signal on RCT.
8. Return to normal:
a. Reset DCT to normal position.
b. Reset RCT - press reset button.
c. Reset control module to Normal: Press and hold the
“DELAY/Reset/Silence” button for 3 seconds; Power
LED and Sounder quickly pulse 3 or 5 times, then
Power LED remains GREEN steady-on.
009180
RETURN TO NORmAL
STATUS
RESET DCT, RCT, AND
CONTROL MODuLE
POWER LED IS GREEN
STEADY-ON
009180d
CONTROL mODULE
COmPLETES TImE
DELAY
PuSH BuTTON
DuRING RELEASE
ACTIVATED (RED
LED AND SOuNDER
ARE STEADY-ON)
• vERIfy No
RESPONSE TO
PuSHING BuTTON
009180b
SET DCT TO
ALARm TO TEST
TImE DELAY
BEFORE END
OF TIME DELAY,
PuSH BuTTON
TO RESTART
TIME DELAY (MAY
PuSH BuTTON
MuLTIPLE TIMES
AS NEEDED)
009180
RETURN TO
NORmAL STATUS
RESET DCT, RCT,
AND CONTROL
MODuLE
POWER LED IS
GREEN STEADY-ON