SECTION 3 – USER INTERFACE
2014-APR-30 REV. 0 PAGE 3-1
USER INTERFACE
This section provides the user with overall information on
features and operation of the CHECKFIRE 110 Control
Module.
FIELD CONNECTIVITY – Cables and Devices
The CHECKFIRE 110 Control Module communicates to
devices through cable assemblies incorporating IP67 circu-
lar threaded connectors with color-coded overmolding. See
Figure 3-1.
IP67 is an environmental ingress protection rating. The first
number indicates protection from solid objects (0 is no special
protection, 6 is protection from dust). The second number is
protection against liquids (0 is no protection, 7 is protection
against the effect of immersion in water).
Detection Circuit Lead
• 33 in. (838 mm) Cable
• Red color-coded IP67 anti-vibration connector (Female)
Release Circuit Lead
• 27 in. (686 mm) Cable
• Blue color-coded IP67 anti-vibration connector (Female)
External Power Circuit Lead (12/24 VDC)
• 21 in. (533 mm) Cable
• Green color-coded IP67 anti-vibration connector (Male)
Alarm Circuit Lead (Auxiliary Devices)
• 3.3 VDC digital output
• 16 in. (406 mm) Cable
• Yellow color-coded IP67 plug
FIGURE 3-1
CONTROL MODULE LEADS
009150
CONTROL MODULE FRONT PANEL BUTTONS
“DELAY/Reset/Silence” Button
Manage fault and/or detection conditions by pressing the
“DELAY/Reset/Silence” button (See Figure 3-2) for the follow
-
ing results:
• Audible Fault Silence
o Silence an audible notification during a fault condition for
two hours. Fault LED indicator(s) continue pulsing until
the fault condition has been cleared. If a subsequent fault
condition occurs, the audible notification will resume until
the “DELAY/Reset/Silence” button is pressed again or the
fault has cleared.
o During a post-discharge condition the button will silence
the sounder.
o Any new Detection or Fault conditions will reactivate the
audible notification.
o The audible notification for either a post-discharge or fault
condition will resume after being silenced for two hours.
• Restart Time Delay Sequence
Restart the time delay cycle during a Detection condition
(must be initiated before release circuit activation occurs).
• Control Module Reset
Reset the control module after initiating devices have been
restored and/or reset.
• Select Time Delay Period
Two options available: 5 seconds or 15 seconds
FIGURE 3-2
CONTROL MODULE FRONT PANEL
009180
CHECKFIRE 110
Detection and Actuation System
3.3 VDC ALARM
OUTPUT
ExTERnAL
POwER
RELEASE
(DuST CAP)
DETECTIon
“PuSh To ACTIVATE/ALARM whEn
LIT” BuTTon AnD LED InDICAToR
“DELAY/RESET/
SILEnCE” BuTTon