Waterflow Circuit Operation
3. Operation of the Control Panel
IQ-636X Operations Manual P/N 52181:A 04/28/2005
39
Silence Inhibit Timer
A timer that disables the
SIGNAL
SILENCE
key function for the programmed time (0-300 seconds) when
a fire alarm occurs. A Silence Inhibit Timer starts at the first fire alarm and restarts with each new fire
alarm.
Waterflow Circuit Operation
If a monitor module programmed with a
WATERFLOW
Type Code initiates a fire alarm, the control panel
disables the
SIGNAL
SILENCE
key and the Auto Silence Timer. Refer to the
IQ-636X Installation Manual
for information on Waterflow circuits.
Style 6 and Style 7 Operation
Style 6 and Style 7 are supervised methods of communicating with addressable devices. If the control
panel detects a trouble (open or short), it will drive both ends of the loop, maintaining communication in
an unsupervised method. The latching trouble will display on the panel as a Style 6 trouble until you
correct the condition and press reset. Style 7 configuration of the SLC requires the use of ISO-X
modules.