7  TROUBLE SHOOTING 

Problem 

LCD/LED/Buzzer 

Explanation / Possible cause 

What to do 

Unit shuts down 
automatically 
during startup 
process. 

LCD/LEDs and buzzer 
will be active for 3 
seconds and then 
complete off. 

The battery voltage is too low 
(<1.91V/Cell)

 

1. Re-charge battery. 
2. Replace battery. 

No response after 
power on. 

No indication. 

1. The battery voltage is far too 
low. (<1.4V/Cell) 
2. Internal fuse tripped. 

1. Contact repair center for 
replacing the fuse. 
2. Re-charge battery. 
3. Replace battery. 

Mains exist but the 
unit works in 
battery mode. 

Input voltage is 
displayed as 0 on the 
LCD and green LED is 
flashing. 

Input protector is tripped 

Check if AC breaker is tripped 
and AC wiring is connected 
well. 

Green LED is flashing. 

Insufficient quality of AC power. 
(Shore or Generator) 

1. Check if AC wires are too 
thin and/or too long. 
2. Check if generator (if 
applied) is working well or if 
input voltage range setting is 
correct. (UPS

Appliance) 

Green LED is flashing. 

Set “Solar First” as the priority of 
output source. 

Change output source priority 
to Utility first. 

When the unit is 
turned on, internal 
relay is switched on 
and off repeatedly. 

LCD display and LEDs 
are flashing 

Battery is disconnected. 

Check if battery wires are 
connected well.   

Buzzer beeps 
continuously and 
red LED is on. 

Fault code 07 

Overload error. The inverter is 
overload 110% and time is up. 

Reduce the connected load by 
switching off some 
equipment. 

Fault code 05 

Output short circuited.   

Check if wiring is connected 
well and remove abnormal 
load.   

Temperature of internal converter 
component is over 120°C. 

Check whether the air flow of 
the unit is blocked or whether 
the ambient temperature is 
too high. 

Fault code 02 

Internal temperature of inverter 
component is over 100°C. 

Fault code 03 

Battery is over-charged.   

Return to repair center. 

The battery voltage is too high. 

Check if spec and quantity of 
batteries are meet 
requirements. 

Fault code 01 

Fan fault 

Replace the fan. 

Fault code 06/58 

Output abnormal (Inverter voltage 
below than 190Vac or is higher 
than 260Vac) 

1. Reduce the connected 
load. 
2. Return to repair center 

Fault code 
08/09/53/57 

Internal components failed. 

Return to repair center. 

Fault code 51 

Over current or surge. 

Restart the unit, if the error 
happens again, please return 
to repair center. 

Fault code 52 

Bus voltage is too low. 

Fault code 55 

Output voltage is unbalanced. 

Web: anern-marketing.com | Email: [email protected] | Whatsapp: +86 13058030989

Summary of Contents for 3.2KW

Page 1: ...1 3 2KW 5KW HYBRID SMART SOLAR SYSTEM VERSION 1 0 USER MANUAL Web anern marketing com Email marketing anern com Whatsapp 86 13058030989...

Page 2: ...CONNECTION 12 5 OPERATION 13 5 1 POWER ON OFF 13 5 2 OPERATION AND DISPLAY PANEL 13 5 3 LCD DISPLAY ICONS 15 5 4 LCD SETTING 17 5 5 DISPLAY SETTING 24 5 6 OPERATING MODE DESCRIPTION 27 5 7 BATTERY EQU...

Page 3: ...ON Only qualified personnel can install this device with battery 6 NEVER charge a frozen battery 7 For optimum operation of this inverter charger please follow required spec to select appropriate cabl...

Page 4: ...ority via LCD setting Compatible to mains voltage or generator power Auto restart while AC is recovering Overload Over temperature short circuit protection Smart battery charger design for optimized b...

Page 5: ...display 2 AC output Reserve 3 Power on off switch 4 DC breaker 5 PV input 6 AC output 7 AC input 8 Communication port 9 GND terminal 10 Circuit breaker Web anern marketing com Email marketing anern co...

Page 6: ...1 Users can set up their own external batteries according to their own needs 2 The external battery pack voltage shall be in line with the system requirement voltage 3 2KW 24V 5KW 48V Battery capacity...

Page 7: ...ble construction materials Mount on a solid surface Install this inverter at eye level in order to allow the LCD display to be read at all times For proper air circulation to dissipate heat allow a cl...

Page 8: ...W 5KW 1 x 2AWG 35 2 Nm Please follow below steps to implement battery connection 1 Remove insulation sleeve 18 mm for positive and negative conductors 2 Suggest to put bootlace ferrules on the end of...

Page 9: ...del Gauge Cable mm2 Torque Value 3 2KW 12 AWG 4 1 2 Nm 5KW 10 AWG 6 1 2 Nm Please follow below steps to implement AC input output connection 1 Before making AC input output connection be sure to open...

Page 10: ...Vmp 30 1Vdc Imp 8 3A Voc 37 7Vdc Isc 8 4A Cells 60 SOLAR INPUT Q ty of panels Total input power Min in serial 6 pcs max in serial 13 pcs 6 pcs in serial 6 pcs 1500W 8 pcs in serial 8 pcs 2000W 12 pcs...

Page 11: ...11 Web anern marketing com Email marketing anern com Whatsapp 86 13058030989...

Page 12: ...stalled from APP store and Refer to Wi Fi Plug Quick Installation Guideline to set up network and registering The inverter status would be shown by mobile phone APP or webpage of computer 3 GPRS cloud...

Page 13: ...he front panel of the inverter It includes three indicators four function keys and a LCD display indicating the operating status and input output power information LED Indicator LED Indicator Messages...

Page 14: ...the inverter Function Keys Function Key Description ESC To exit setting mode UP To go to previous selection DOWN To go to next selection ENTER To confirm the selection in setting mode or enter settin...

Page 15: ...and discharging current Battery Information Indicates battery level by 0 24 25 49 50 74 and 75 100 in battery mode and charging status in line mode In AC mode it will present battery charging status...

Page 16: ...on Indicates overload Indicates the load level by 0 24 25 49 50 74 and 75 100 0 24 25 49 50 74 75 100 Mode Operation Information Indicates unit connects to the mains Indicates unit connects to the PV...

Page 17: ...ficient to power all connected loads utility will supply power to the loads at the same time Battery provides power to the loads only when any one condition happens Solar energy and utility is not ava...

Page 18: ...up in program 26 27 and 29 06 Auto restart when overload occurs Restart disable default Restart enable 07 Auto restart when over temperature occurs Restart disable default Restart enable 09 Output fre...

Page 19: ...2 5V 23 0V default 23 5V 24 0V 24 5V 25 0V 25 5V Available options in 5KVA model 44V 45V 46V default 47V 48V 49V 50V 51V 13 Setting voltage point back to battery mode when selecting SBU priority or So...

Page 20: ...6V 26 5V 27V default 27 5V 28V 28 5V 29V Available options in 5KVA model Battery fully charged 48V 49V 50V 51V 52V 53V 54V default 55V 56V 57V 58V Web anern marketing com Email marketing anern com Wha...

Page 21: ...or Power saving mode only solar energy can charge battery Solar energy will charge battery if it s available and sufficient 18 Alarm control Alarm on default Alarm off 19 Auto return to default displ...

Page 22: ...from 25 0V to 31 5V for 3 2KVA model and 48 0V to 61 0V for 5KVA model Increment of each click is 0 1V 29 Low DC cut off voltage 3 2KVA default setting 21 0V 5KVA default setting 42 0V If self define...

Page 23: ...lected in this program it s to activate battery equalization immediately and LCD main page will shows If Disable is selected it will cancel equalization function until next activated equalization time...

Page 24: ...tage output voltage output frequency load percentage load in Watt load in VA load in Watt DC discharging current main CPU Version Selectable information LCD display Input voltage Output voltage Defaul...

Page 25: ...arging current 50A PV charging current 50A AC charging current 50A Charging power AC and PV charging power 500W PV charging power 500W AC charging power 500W Web anern marketing com Email marketing an...

Page 26: ...t frequency 50Hz Load percentage Load percent 70 Load in VA When connected load is lower than 1kVA load in VA will present xxxVA like below chart When load is larger than 1kVA 1KVA load in VA will pre...

Page 27: ...checking Main CPU version 20 09 5 12 Operating Mode Description Operation mode Description LCD display Standby mode Power saving mode Note Standby mode The inverter is not turned on yet but at this ti...

Page 28: ...V energy No charging Operation mode Description LCD display Line Mode The unit will provide output power from the mains It will also charge the battery at line mode Charging by utility and PV energy T...

Page 29: ...e buildup of negative chemical effects like stratification a condition where acid concentration is greater at the bottom of the battery than at the top Equalization also helps to remove sulfate crysta...

Page 30: ...tage at the battery equalization voltage The battery will remain in the Equalize stage until setting battery equalized time is arrived However in Equalize stage when battery equalized time is expired...

Page 31: ...oft start failed 55 Over DC voltage in AC output 57 Current sensor failed 58 Output voltage is too low 59 PV voltage is over limitation 5 15 Warning Indicator Warning Code Warning Event Audible Alarm...

Page 32: ...ac 7V Max AC Input Voltage 300Vac Nominal Input Frequency 50Hz 60Hz Auto detection Low Loss Frequency 40 1Hz Low Loss Return Frequency 42 1Hz High Loss Frequency 65 1Hz High Loss Return Frequency 63 1...

Page 33: ...r for 5 seconds Nominal DC Input Voltage 24Vdc 48Vdc Cold Start Voltage 23 0Vdc 46 0Vdc Low DC Warning Voltage load 50 23 0Vdc 46 0Vdc load 50 22 0Vdc 44 0Vdc Low DC Warning Return Voltage load 50 23...

Page 34: ...inimum 10mins maximum 8hrs T0 2 43Vdc 2 35Vdc 2 25Vdc MPPT Solar Charging Mode INVERTER MODEL 3 2KW 5KW Max PV Array Power 4000W 4000W 5000W Option Nominal PV Voltage 240Vdc PV Array MPPT Voltage Rang...

Page 35: ...nd off repeatedly LCD display and LEDs are flashing Battery is disconnected Check if battery wires are connected well Buzzer beeps continuously and red LED is on Fault code 07 Overload error The inver...

Page 36: ...7 Model Load W Backup Time 48Vdc 100Ah min Backup Time 48Vdc 200Ah min 5KW 500 613 1288 1000 268 613 1500 158 402 2000 111 271 2500 90 215 3200 76 182 3500 65 141 4000 50 112 4500 44 100 5000 40 90 No...

Page 37: ...37 327 100003 00G Web anern marketing com Email marketing anern com Whatsapp 86 13058030989...

Reviews: