18IP22B
25
5.2.4
Flues
Type
Water flow rate Q
Pressure drop H in
in m /h
meter water gauge
3
132
48
4,7
154
47
4,6
180
46
4,5
210
45
4,4
244
44
4,3
280
43
4,2
Table 5 Water flow rate and pressure drop
Type
Grundfos
Pump motor rating
pump
132
154
180
DNM 65 -
210
125/136
244
280
3N~ 400 V
0,75 kW
1410 r.p.m.
2,22 A
Table 6 Pump motor rating
The water heater is supplied with a primary pump and must
have a separate secured electrical supply (3 x 400 V) is nor-
mally required for the primary pump.
Tolerance on voltage: 400 V +10 % /-15 %
Flue dimensions
The water heater has its own integral draught diverter and does
not require any other draught diverter in the flue.
The flue socket at the top of the water heater is sized for the
direct attachment of single wall metal flue pipe.
Optional adapters can be obtained for twin wall metal pipe and
BS 835 type flue pipe. It is recommended that the water heater
be connected to it’s own individual open flue systems, although
some open flue systems can be used for multiple installations
of the same type of water heater.
This section should be used for guidance only. A flue specialist
should be contacted to rate a flue design.
You can use the following flue dimensions to assist in flueing:
Type
Q flue m /h
Chimney
3
diameter mm
132
1770
450
154
2062
500
180
2421
550
210
2811
600
244
3270
650
280
3751
700
Table 7 Flue gas volumes
Heat input:
100 %
Flow temperature:
90 °C
Return temperature
70 °C
Flue gas temperature:
130 °C
CO
5,5 %