Maintenance
67
MAXXflo EVO
6.2.14 CIRCuLATION PuMP Q1
• Close the shut off valve before and after the pump.
• Use the drain points between the shut off valves to remove water from the pump
• Remove the PWM and power connectors, using a small flat blade screwdriver to lift the white tab before
pulling each connector free.
• Undo the unions at the top and bottom of the pump body and remove pump.
• Fit the new pump seals
• Replacement is the reverse
• Refill and bleed of air
• Operate the pump by pulling the electrical connector off the heat exchanger front flow sensor (B2)
• When all sound of air has stopped, reconnect B2 sensor and press the reset for around one second
Pump Union
Pump Union
B2 Sensor