MAXXflo Water Heater
36
36
A fault code will appear in the control panel display if there
is a lockout failure. A letter and the number of the burner
module appear alternately in the display. The letter A is for
a lockout fault and E is for a blocking fault. The two right
segments show a fault code, table 2 gives the meaning
of the different codes. If there is a fault in more than one
burner module, the display alternates every 5 seconds
between burner modules and their associated fault codes.
Lockout faults can be reset using the reset button. Only
the burner module for which the fault code appears in the
display at that moment is reset. Any E code (or blocking
fault) will require some form of rectification before it can be
reset, i.e. repair or replacement of a component or part. An
E code could indicate a fault in connection with the Master
or Slave boards.
FAULT CODES
MASTER BOARD BLOCKING CODES
E09
Control Error: Internal RAM location not correct
E12
Control Error: The incorrect parameters are
programmed in the slave board
E13
Control Error: A references measurement
indicated that the AD-circuit is defective, too low
E14
Control Error: A references measurement
indicated that the AD-circuit is defective, too
high
E15
Control Error: A references measurement
indicated that the AD-circuit is defective, too low
E16
Control Error: A references measurement
indicated that the AD-circuit is defective, too
high
E18
Control Error: Internal RAM
E19
Control Error: Not able to read parameters
E20
No slave board present
E22
Power Fault: The 50Hz has too large deviation
E60
Tank sensor opened circuit
E65
Return sensor opened circuit
E70
Tank sensor shorted
E75
Return sensor shorted
SLAVE BOARD BLOCKING CODES
E0
Read Error: Not able to read stored parameters
E28, E29, Control error: Reference measurements
E30, E31 indicates that there is an error in the AD circuit
E33
Flame detected when gas valve was closed
E41
Phase Error: Live and neutral reversed
E42
Phase Error: Too much deviation in the supply
voltage frequency
E44
Control Error: Poor communication between the
two processors
E47
Return sensor open circuit
E48
Flow sensor open circuit
E63
Return sensor short circuit
E64
Flow sensor short circuit
E78
Reset Error: Too many user resets
SLAVE BOARD LOCKOUT CODES
A01
Three Failed Ignitions: After three ignitions,
there was still no flame detected
A02
Overheat Stat Failure: No water flow conditions,
the flow sensor is not detecting a temperature
increase during operation
A03
The two flow sensors have too greater
temperature differential between them, 10°C for
more than 60 seconds
A05
Gas Valve Relay Error: The gas valve relay is not
switching correctly
A06
Safety Relay Error: The safety relay is not
switching correctly
A08
Fan Error: The fan is not reaching its target value
or speed for more than 60 seconds
A09
Control Error: Internal storage location
A10
The contents of the stored parameters are not
correct
A11
Flow Temperature: Flow temperature went above
95°C
A12
Control Error: The stored contents inside the
control are not matching the software version
A14
Control Error: Internal storage location
A15
Control Error: Internal storage location
A16
Control Error: Internal storage location
A17
Control Error: Internal storage location
A19
Control Error: Internal storage location
A20
Flame detection after gas valve is closed. Flame
still present 10 seconds after the gas valve is
closed
A21
Flame detected before opening of the gas valve
during the start up sequence
A24
Too many flame failures: When the flame fails
three times within on burn cycle
SECTION 6 • FAULT CODES
Summary of Contents for CWH120/200
Page 8: ...MAXXflo Water Heater 8 8 INSPECTION HATCH INSPECTION HATCH SECTION 2 TECHNICAL DETAILS ...
Page 9: ...MAXXflo Water Heater 9 9 TECHNICAL DETAILS SECTION 2 INSPECTION HATCH INSPECTION HATCH ...
Page 28: ...MAXXflo Water Heater 28 28 FLUE SYSTEMS Fig 12 SECTION 3 INSTALLATION ...
Page 39: ...MAXXflo Water Heater 39 39 PARTS LIST SECTION 8 MAXXflo INTERNAL SPARES ITEMS ...