MAXXflo Water Heater
27
27
INSTALLATION • SECTION 3
FLUE SYSTEMS
Fig 11
Terminal position description
Minimum distance (mm)
Type Cxx flue systems
CWH30,
CWH60
CWH90
CWH120
A
Directly below an opening, air brick, opening window etc
300
2,500
2,500
B
Above an opening, air brick, opening window etc
300
700
900
C
Horizontal to an opening, air brick, opening window etc
300
700
900
D
Below a gutter or sanitary pipework etc
75
200
200
E
Below the eaves
200
200
200
F
Below a balcony or carport roof
200
Not reco
G
Above ground, roof or balcony level
300
300++
300++
H
From vertical drain/soil pipework
150
150
150
J
From an internal or external corner
300
300++
300++
K
From a surface or boundary facing a terminal
1,200
2,300
2,800
L
Vertically from a terminal on the same wall
1,500
2,500
2,500
M Horizontally from a terminal on the same wall
300
700
900
N
From a surface or boundary facing a terminal
600
2,600
3,200
P
From an opening in a carport (e.g. door, windows) into the building
1,200
Not reco
Q
Above a pitched roof
300
400
500
R
From a vertical structure on a roof
2,500
2,500
2,500
S
Above a flat roof
300
400
500
From any other roof flue terminal
300
700
900
+ Not recommended - Risk assessment required
++ Plume management recommended
Summary of Contents for CWH120/200
Page 8: ...MAXXflo Water Heater 8 8 INSPECTION HATCH INSPECTION HATCH SECTION 2 TECHNICAL DETAILS ...
Page 9: ...MAXXflo Water Heater 9 9 TECHNICAL DETAILS SECTION 2 INSPECTION HATCH INSPECTION HATCH ...
Page 28: ...MAXXflo Water Heater 28 28 FLUE SYSTEMS Fig 12 SECTION 3 INSTALLATION ...
Page 39: ...MAXXflo Water Heater 39 39 PARTS LIST SECTION 8 MAXXflo INTERNAL SPARES ITEMS ...