Maintenance
61
MAXXfl o EVO 150/302
6.2 REMOVING AND CHANGING COMPONENTS
DANGER
NONE OF THE CONTROLS ARE REPAIRABLE . IF THEY ARE NOT FUNCTIONING THEY MUST
BE REPLACED In all cases, before work commences turn off the mains electricity and gas supply.
The following items do not require isolating water before removal:
1. DHW tank temperature sensor
2. Flue temperature sensor
3. Common fl ow temperature sensor
4. GUI display
5. Master & Slave controller PCB
6. Spark generator
7. Combustion fan
8. Gas valve
9. Spark & Ionisation electrodes
10. Back fl ow prevention air intake valve
11. Overheat thermostat
The following items require isolation of water before removal and bleeding air afterwards:
12. Heat exchanger
13. Internal circulation pump
14. Water pressure sensor
6.2.1 DHW TANK TEMPERATURE SENSOR (B3)
• Remove tank sensor access panel located at low level on LH side of heater (refer to section 5.5.2).
• Gently remove and pull the cable sensor out of the sensor well whilst feeding it down through the ‘P’
clip so that it can hang free. (note: There is no need to loosen the screw holding the ‘P’ clip)
• Undo the bulkhead seal located at high level on LH side of bulkhead (removal of PCB cover panel is
required). Gently pull the sensor up and through the bulkhead seal.
• Unplug connector from loom.
• Remove sensor.
• Replacement is the reverse.
Bulkhead seal
Sensor connector
Sensor cable
Sensor well
‘P’ clip