Hardware Installation
DCX 250 Installation Guide
13
Figure 7 illustrates how to wire the Infinet cable to the block terminal
connector.
Figure 7. Infinet Cable Wiring
3. Trim back the shield over the wires.
4. Slip the first wire from the incoming Infinet cable and the first wire
from the outgoing Infinet cable into the hole beneath the screw
labeled with a plus sign.
5. Tighten the screw down on it until the screw holds the wires in place.
6. Slip the second (usually black) wire from each Infinet cable under
the screw labeled with a minus sign (middle) and tighten the screw
down on them.
7. Slip the shields from the incoming and outgoing Infinet cables under
the screw labeled SHLD and tighten the screw down on them.
Wiring the Infinet to the Infinity CX 9000
You connect the last piece of Infinet cabling to the Infinity CX 9000 as
explained in the Andover Controls Infinity CX 9000 Hardware
Installation Guide.
+
–
SHLD
Infinet Connection
WHITE
WHITE
BLACK
BLACK