ANDERSON-NEGELE MPI-200 Product Information Download Page 7

C O N T R O L S

7

Troubleshooting

Problem

Check

Solution

The device does not appear in the 

parameter structure

Are the MPI-200 and the sensor con-

nected correctly?

Check the cabling.

The program should automatically de-

tect that a device has been connected 

or disconnected. If not, this function 

can be manually activated.

Clicking on the “Reconnect” button 

prompts the program to read in the 

device structure again.

If the USB connection was detected by 

the operating system, the COM no. ap-

pears in the bottom status line under 

“Uart:” ?

Disconnect the USB cable from the PC 

and reconnect it.

If the USB driver was correctly in-

stalled, the adapter is listed in the 

Device Manager.

If the system asks for a manufacturer 

CD, please insert the supplied CD 

and specify the “FTDI” path of the CD 

drive.

Is an external power supply is con-

nected to the M12 connector of the 

MPI or is the “Power supply MPI-200” 

parameter set to “PC”?

Set the appropriate power supply.

Error message when the software is 

started

Is .NET 4.0 or higher installed on the 

PC?

Install .NET from the supplied CD, 

path “NET4.0”.

Error message “The COMx connec-

tion does not exist”

Was the MPI-200 connected just 

before the program was started?

(The operating system detects the 

USB device while the program is being 

started.)

Start the program before connecting 

the MPI-200 or wait until the operat-

ing system has detected the USB 

device.

Editing buttons are inactive

Depending on the parameter, some 

functions may be blocked or unavail-

able. In this case, the buttons are 

deactivated.

Not all process values or parameters 

appear in the menu tree

Is the mode set as required?

Set the mode to the required ap-

plication. Depending on the setting, 

certain modes may be password 

protected.

“Load/save PC settings” menu item

Only the settings for the PC user inter-

face are stored on the hard disk.

In a later software version, it will 

also be possible to save and load the 

parameters of a connected device.

Troubleshooting

Summary of Contents for MPI-200

Page 1: ...her requirement CD drive for program installation Access rights Administrator rights for installation Installing the software 1 Insert the CD included with the MPI 200 into the CD drive 2 Double click...

Page 2: ...external M12 connected A supply from the PC would otherwise be superimposed on the 4 20 mA output signal and lead to an incorrect measur ing signal Electrical connection Power supply Connecting the se...

Page 3: ...t Reconnect Establishing a connection with a sensor reading in the parameter structure again manually Mode Mode setting Monitoring Process values and service information can be viewed but not changed...

Page 4: ...ed e g 4 mA for a mA setpoint Save parameter The manually created setting is adopted and the display returns to the main menu Discard parameter The setting is not adopted and the display returns to th...

Page 5: ...at can only be set to xed values By pressing the arrow buttons Only values that are greater than the cur rently displayed value are possible Only values less than the currently displayed value are pos...

Page 6: ...out and saved After the language and the printer are selected in the option field 3 the process can be completed by clicking the OK button 1 2 3 Export function of the parameter list After the print m...

Page 7: ...supply MPI 200 parameter set to PC Set the appropriate power supply Error message when the software is started Is NET 4 0 or higher installed on the PC Install NET from the supplied CD path NET4 0 Er...

Page 8: ...te Note the cleaning information To avoid damage of the equipment use suitable trans port packaging only Transport storage Do not store outside Store in an area that is dry and dust free Do not expose...

Reviews: