Wiring and Specifying Address and Data Rate
Wiring and Specifying Address and Data Rate
Wiring and Specifying Address and Data Rate
Wiring and Specifying Address and Data Rate
Caution
Turn off the network power supply before making any changes.
It is recommend that you use compression terminal parts.
Connect V+ and V- of the network power wires to the male connector.
Connect CAN_H and CAN_L of signal wires to the male connector.
Connect Drain (shield) to male connector.
Insert and fix the connector.
Specify a node address.
Specify a baud rate.
4.1.3.
4.1.3.
4.1.3.
4.1.3.
Outline of Physical Connection for DeviceNet
Outline of Physical Connection for DeviceNet
Outline of Physical Connection for DeviceNet
Outline of Physical Connection for DeviceNet
This slave device consumes maximum 55 mA from the network.
Install terminating resistor at both ends of the trunk.
When thin cable is used, the maximum cable distance of the trunk is less than 100 m.
When thick cable is used, the maximum cable distance relates to the data rate
The length of the drop line should be less than 6 m. The total length of the drop lines
relates to the data rate.
Connect the drain line to the ground terminal of the power tap, and ground them.
Data rate and Cable Distance
Maximum Cable Distance
Trunk Line
Dorp Line
Data Rate
Thin Cable
Thick Cable
A Drop Length Cumulative Length
125 kbps
500 m
156 m
250 kbps
250 m
78 m
500 kbps
100 m
100 m
39 m
6 m