Page 4
AD-4402 OP-21
3.
3.
3.
3.
Panel and Names
Panel and Names
Panel and Names
Panel and Names
3.1.1.
3.1.1.
3.1.1.
3.1.1.
Node Address and
Node Address and
Node Address and
Node Address and Data
Data
Data
Data Rate
Rate
Rate
Rate
Node Address
Set a node address for this slave device using binary switches (2
0
to 2
5
).
The node address range is 0 to 64.
Example: If address is 44, turn on the swithes of 32, 8, 4 (2
5
, 2
3
, 2
2
).
Data Rate (Baud Rate)
Set a data rate using switch DR0 and DR1.
Data rate
125 kbps
250 kbps
500 kbps
Not used
DR0
OFF
ON
OFF
ON
DR1
OFF
OFF
ON
ON
Status LED
These LEDs indicate situation of the interface.
MS (Module Status)
NS (Network Status)
Green ON
Device operational
On-line
Flashing Green
Not connected
Red ON
Unrecoverable fault
Critical link fault
Flashing Red
Recoverable fault
Connection time-out
3.1.2.
3.1.2.
3.1.2.
3.1.2.
Connector (Terminal)
Connector (Terminal)
Connector (Terminal)
Connector (Terminal)
The connector style is the pluggable open connector. This connector consists of a
male connector and a female connector.
Female Connector
Pin Color
Symbol
Description
1
Black
V-
Power-
2
Blue
CAN_L
Signal low
3
Bare
Drain
Shield
4
White
CAN_H
Signal high
5
Red
V+
Power+
Male Connector
Connector of cable side
(Accessory)
NODE ADDRESS
switches (1 to 32)
D
ata
R
ate switch (0, 1)
MS
Module Status LED
NS
Network Status LED
Summary of Contents for Device Net.Interface AD-4402 OP-21
Page 1: ...ふ Interface WM PD4000301 ...
Page 26: ...Page 24 AD 4402 OP 21 MEMO ...