ANATEL Novus RHT-Air Instruction Manual Download Page 7

NOVUS AUTOMATION 

7/10 

REGISTER 29 – BATTERY POWER 

It has the value of measuring the voltage level of the battery in engineering 

unit. The decimal point is fixed in three houses. The value is without the 

point and must be predicted by the reading software. Reading the battery 

voltage may show an error of up to 5 %. 
Typically, a battery with 100  % of its load has voltage above 3.6V. 

Depending on the use of 

RHT-Air

, the battery will gradually decrease 

voltage. It is recommended to periodically check the value of this register so 

that, when it reaches values below 3.3 V, a battery change is scheduled. 
Checking the battery capacity can be done using the 

Diagnostics

 tab of the 

DigiConfig

 software, which will display an icon. The evaluation of battery 

capacity can be performed according to the criteria presented in the table 

below: 

REGISTER VALUE 

BATTERY 

CAPACITY 

ICON

 

USB-connected 

device. 

 

3500 to 3700 

Great 

 

3400 to 3500 

Very Good 

 

3300 to 3400 

Good 

 

3200 to 3300 

Average – Get ready 

to replace your 

battery. 

 

Lower than 3200 

Bad – Replace the 

battery as soon as 

possible. 

 

NOTE 1

: Even when the power is below 100 %, the device will operate normally.  

NOTE 2

: The gradual failure of the battery power is not linear, therefore, though the device 

is able to continue working under tensions below 3.0 V, when it reaches this level, there is 

little left for its life, since the power will fail more quickly. 

NOTE 3

: While the device is being powered from an external source, you may notice a 

slight rise in battery voltage. This is because the battery voltage increases whenever power 

from the same battery is not being consumed. 

NOTE 4

: The machine operating temperature has a significant impact on the battery 

capacity. Temperatures below 0 °C will typically shorten the battery life. 

NOTE  5

:  Battery chemistry is directly affected by the ambient temperature. High 

temperatures tend to raise battery voltage, as low temperatures tend to decrease 

battery voltage. In both cases, autonomy is negatively affected. 

NOTE 6

: The update time, as well as the operating power, have a significant impact on 

the battery  capacity. If the device is configured for the lowest update interval, the 

battery will typically last less. The  same happens when the device is  far from the 

AirGate-Modbus

  with which it should be matched, needing a higher transmission 

power to operate. 

NOTE 7

: Remove the battery or insert the insulation film when the device is not in use. 

Leaving the powered device out of range of a Wireless network will cause the device to 

continually attempt to pair, which may lead to premature battery death. 

REGISTER 30 – LAST POLL DURATION 

Every time 

RHT-Air

 publishes something on 

AirGate-Modbus

, this register 

gets a zero  value. Every 100 ms, this register is increased in 1 unit to 

indicate how long it has been since the last publication. 

REGISTER 31 – MODBUS ADDRESS 

It sets the address of the device on the Modbus network. This address 

identifies the device on  the Modbus network. Its configuration may range 

from 1 and 247. There cannot be more than one piece of device with the 

same address on the same network. 

RHT-Air

 is originally manufactured with 

the address 246. When connected to a USB interface, it always responds to 

Modbus functions through the address 246. When it is in operation, it always 

responds through the address it was configured for in this register according 

to the communication parameters of the Modbus network on which it was 

installed. 

REGISTER 32 – UPDATE TIME 

It sets the configuration for how often the device wakes  to  publish 

information on the 

AirGate-Modbus

 with which it is matched and update the 

IHM screen.  
The shorter the update time, the more recent the data available to the 

master of the Modbus network will be, but the higher the energy 

consumption spent, and the battery life will be proportionately shorter. On 

the other hand, the higher the update time set, the lower the energy 

consumption spent will be, thus providing a longer life for the battery. 

REGISTER 33 – INDICATION MODE 

It sets the mode of indication of the values read on the display. The device is 

originally manufactured with the indication of temperature and relative 

humidity. 

CODE 

DESCRIPTION 

Indicates the temperature and relative humidity. 

Indicates the temperature and dew point. 

Indicates relative humidity and dew point. 

Indicates the temperature only. 

REGISTER 34 – CONFIGURATION OF THE MEASUREMENT UNIT 

It sets the measurement unit for both temperature and dew point. The device 

is originally configured in (°C). 

CODE 

UNIT 

°C 

°F 

REGISTER 35 – DISABLES CONFIGURATION THROUGH A BUTTON 

It sets the alteration of configuration through a button. 

CODE 

DESCRIPTION 

Factory default value. 

Disables the alteration  of configuration of communication 

parameters via button. 

REGISTER 36 – USER OFFSET FOR TEMPERATURE 

It sets the users’  offset value in engineering units for temperature. The 

device offset value is originally zero. 

REGISTER 37 – USER OFFSET FOR HUMIDITY 

It sets the users’  offset value in engineering units for relative humidity.  The 

device offset value is originally zero. 

REGISTER 38 – ERROR VALUE 

It contains the error value that is transmitted when the sensor has a problem. 

The device original value is -9999. 

REGISTER 39 – TEMPERATURE VALUE (°C or °F) 

It contains the value of temperature measurement in an engineering unit, 

including the users’ offset corrections for temperature. The decimal point is 

fixed in one place. The value has no point and must be provided in the 

reading software. 

REGISTER 40 – RELATIVE HUMIDITY VALUE (%) 

It  contains the value of relative humidity measurement in an engineering 

unit, including the users’ offset corrections for temperature. The decimal 

point is fixed in one space. The value has no point and must be provided in 

the reading software. 

REGISTER 41 – DEW POINT VALUE (°C or °F) 

It has the value of the measurement in an engineering unit. The decimal 

point is fixed in one place. The value has no point and must be provided in 

the reading software. 

Summary of Contents for Novus RHT-Air

Page 1: ...NOVUS AUTOMATION 1 10 RHT Air WIRELESS DEVICE FOR TEMPERATURE RELATIVE HUMIDITY AND DEW POINT INSTRUCTIONS MANUAL V2 0x A...

Page 2: ...212 F Relative Humidity RH 0 0 to 100 0 RH No condensation Dew Point 40 C and 100 C 40 F to 212 F Measurements Accuracy See Figure 3 Note It is possible to perform an Offset adjustment using the DigiC...

Page 3: ...one through USB interface Remove the four set screws of the front panel of the RHT Air device taking the necessary precaution not to apply force on the internal connector of the electronic circuit Fig...

Page 4: ...register When it reaches values below 3 3 V a battery change must be scheduled this register may present a measurement error of up to 5 Note Even when the power is below 100 the device will operate n...

Page 5: ...y 8 Screen Dew point 7 WIRELESS COMMUNICATION RHT Air has an IEEE 802 15 4 wireless communication to connect to AirGates Modbus that has its firmware updated to a version more recent than V1 23 The fi...

Page 6: ...z 21 2455 MHz 22 2460 MHz 23 2465 MHz 24 2470 MHz 25 2475 MHz REGISTER 28 LINK QUALITY INDICATOR It serves to inform the quality of the reception link of the connection between the device and the AirG...

Page 7: ...e Modbus network This address identifies the device on the Modbus network Its configuration may range from 1 and 247 There cannot be more than one piece of device with the same address on the same net...

Page 8: ...rror value 9999 9999 R W 39 Temperature value C or F 400 1000 R 40 Relative humidity value 0 1000 R 41 Dew point value C or F 400 800 R For the abovementioned table ranges one decimal place should be...

Page 9: ...the FCC Rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that...

Page 10: ...NOVUS AUTOMATION 10 10 11 WARRANTY Warranty conditions are available on our website www novusautomation com warranty...

Reviews: