ANATEL Novus RHT-Air Instruction Manual Download Page 6

NOVUS AUTOMATION 

6/10 

REGISTER 16 – POWER LEVEL 

According to the variations presented in the table below, the power level can be 

adjusted as needed. The higher the power set, the greater the range and the 

greater the consumption. It is suggested that the lowest value possible be 

configured, if 

RHT-Air

 is not able to communicate with the 

AirGate-Modbus

, it will 

automatically increase the transmission power gradually, until it is able to 

communicate with 

AirGate-Modbus

 or reach the highest configurable limit. It may 

be that this register is configured with a value, and, after some time, this value 

may be altered to adjust to a communicable power. 

CODE 

POWER LEVEL

 

0 dBm 

2 dBm 

4 dBm 

6 dBm 

8 dBm 

10 dBm 

12 dBm 

14 dBm

 

REGISTER 27 – OPERATION CHANNEL 

It  indicates the operation channel in which the device is operating in the 

network. It may vary from 11 to 25, in that every channel is equivalent to one 

frequency of operation. The network will always operate on the channel with 

less interference among all the 15 possible ones. 

CHANNEL 

OPERATION FREQUENCY

 

11 

2405 MHz 

12 

2410 MHz 

13 

2415 MHz 

14 

2420 MHz 

15 

2425 MHz 

16 

2430 MHz 

17 

2435 MHz 

18 

2440 MHz 

19 

2445 MHz 

20 

2450 MHz 

21 

2455 MHz 

22 

2460 MHz 

23 

2465 MHz 

24 

2470 MHz 

25 

2475 MHz 

REGISTER 28 –

 

LINK QUALITY INDICATOR

 

It serves to inform the quality of the reception link of the connection between the device and the 

AirGate-Modbus

 with which it is matched. This value is obtained by 

measuring the power of the last package received. This power is measured in dBm, which is a logarithmic power unit in mW. The LQI may vary from -100 dBm (worst 

reception quality) to -15 dBm (best reception quality). 
For devices operating in ideal environments where there are no obstacles and no electromagnetic interference, the LQI will behave in a way close to the graph below, 

where the comparison between different power levels is performed for the distance versus LQI ratio. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 13 –

 

Distance x LQI relation for several powers 

The table below lists the values obtained in the LQI reading with the evaluation 

of signal quality. This information can be viewed more intuitively in the 

DigiConfig

 

Diagnostics

 tab. 

REGISTER VALUE 

QUALITY 

ICON

 

USB-connected 

device

 

 

-15 to -60 

Great

 

 

-60 to -70 

Very Good

 

 

-70 to -80 

Good

 

 

-80 to -90 

Regular

 

 

-90 to -100 

Bad

 

 

NOTE

:  The model described in the graphic takes in consideration the propagation 

channel only. LQI may vary due to several factors, such as due to peripheral obstacles 

like trees, buildings and hills that interfere in the propagation channels as explained by 

the Fresnel Zone phenomenon

.  

 

Summary of Contents for Novus RHT-Air

Page 1: ...NOVUS AUTOMATION 1 10 RHT Air WIRELESS DEVICE FOR TEMPERATURE RELATIVE HUMIDITY AND DEW POINT INSTRUCTIONS MANUAL V2 0x A...

Page 2: ...212 F Relative Humidity RH 0 0 to 100 0 RH No condensation Dew Point 40 C and 100 C 40 F to 212 F Measurements Accuracy See Figure 3 Note It is possible to perform an Offset adjustment using the DigiC...

Page 3: ...one through USB interface Remove the four set screws of the front panel of the RHT Air device taking the necessary precaution not to apply force on the internal connector of the electronic circuit Fig...

Page 4: ...register When it reaches values below 3 3 V a battery change must be scheduled this register may present a measurement error of up to 5 Note Even when the power is below 100 the device will operate n...

Page 5: ...y 8 Screen Dew point 7 WIRELESS COMMUNICATION RHT Air has an IEEE 802 15 4 wireless communication to connect to AirGates Modbus that has its firmware updated to a version more recent than V1 23 The fi...

Page 6: ...z 21 2455 MHz 22 2460 MHz 23 2465 MHz 24 2470 MHz 25 2475 MHz REGISTER 28 LINK QUALITY INDICATOR It serves to inform the quality of the reception link of the connection between the device and the AirG...

Page 7: ...e Modbus network This address identifies the device on the Modbus network Its configuration may range from 1 and 247 There cannot be more than one piece of device with the same address on the same net...

Page 8: ...rror value 9999 9999 R W 39 Temperature value C or F 400 1000 R 40 Relative humidity value 0 1000 R 41 Dew point value C or F 400 800 R For the abovementioned table ranges one decimal place should be...

Page 9: ...the FCC Rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that...

Page 10: ...NOVUS AUTOMATION 10 10 11 WARRANTY Warranty conditions are available on our website www novusautomation com warranty...

Reviews: