Specifications
Input
Volts (VDC)
100-350 VDC
Current (max) *
4 Amps w. Inrush Protection
Input Fuse
6.3A 400 VDC
Power Factor
> 0.99 at Full Load
Efficiency
> 90% at Full Load
*Maximum Input Current Specified at 85 VAC
Output
Nominal Voltage
12 VDC
24 VDC
28 VDC
32 VDC
36 VDC
48 VDC
Voltage Range (VDC)**
12.0-15.5
24.0-31.0
28.0-36.2
32.0-41.3
36.0-46.5
48.0-62.0
Output Current
20 A
10 A
8 A
7.5 A
7 A
5 A
Recommended Battery (Amp-
Hours)
100
50
45
40
33
25
Standard. Temperature
Compensation
-15mV/C
-30mV/C
-35mV/C
-40mV/C
-45mV/C
-60mV/C
Number of Battery Banks
1 or 2
Charging Stages
2 or 3 stage (user-selectable)
End of Charge
Float or Rest (user-selectable)
** Actual Output Voltage determined by User Settings or by Charger Firmware
Mechanical
Dimensions
9.5 in./24.1 cm Long x 8.0 in./20.3 cm Wide x 3.25 in./8.3 cm High
Clearance
2.0 in./5.0 cm all around
Weight
6.2 lb / 2.8 kg
Material and Finish
Marine Grade Black Anodized Aluminum with 18-8 Stainless Fasteners
Mounting
Wall or Shelf Mount
Connections
DC Output - 2x Phoenix VDFK Terminal Block (Red and Black)
AC Input - Input Type-D #14AWG Leads (Red: Positive, Black Negative)
Environmental and Safety
Operating Temperature Range
-25°C+ to +40°C (-40°C to +55°C Optional)
Storage Temperature Range
-55°C to +85°C
Humidity
0 - 95% Relative Humidity (non-condensing)
Vibration
Built to meet MIL810g
Emissions
Complies with FCC Class B, Part 15
Isolation
> 1500 VDC Input-Output, Input-Case, Output-Case
Audible Noise
None (Ø db)
Duty Cycle
Continuous
Warranty
Five Years Parts and Labor
Safety
Built to meet ABS, CE, UL458 and CSA 22.2.107.1