Specifications  

UPC20+ Specifications

Power

Self-powered when used with 110/220 VAC

Power input (for control board)

120/240V 

~

, 50-60 Hz, 0.05/0.025A 

-or-

12 VDC, 0.2A max

Power output per relay

• 20A @ 120/240V 

~

, 50-60 Hz (RESISTIVE LOAD)

• 6A @ 277V 

~

, 50-60 Hz (FLUORESCENT BALLAST)

• 1 HP @ 120V 

~

, 50-60 Hz (INDUCTIVE LOAD)

• 2 HP @ 240V 

~

, 50-60 Hz (INDUCTIVE LOAD)

Total Current through both relays 

CAN NOT

 exceed 20 amp.

Maximum operating ambient 
temperature

55°C

Approvals

UL / C-UL / CE

Includes

• 1-, 2-, and 3-button logic modes

• Local test switches with status LEDs

• 120, 240, and 277 VAC control capability

Inputs

• 4 closure inputs, operation defined by mode.

• One IR remote sensor input.

• Motor Control mode alternates between the timed operation of the two 

power relays.

• Power Control mode allows independent control of both power relays.

Control Ports

Two 2400 W power relays. Total combined current through both relays is 20 
Amps.

Input Power Switch (S1)

• Set this switch according to the high voltage wiring that will be connected 

to terminals 5 and 6 on P1. Refer to the

P1 Terminal Connections

section 

on page 7.

• Set switch S1 to the line input voltage value used before applying power to 

the UPC20+.

High Voltage Terminal Block (P1) High voltage input and output wiring for motor or power control.

Low voltage and Control 
Terminal Block (P2)

Contact closure, open-collector or CMOS logic level remote control wiring. 
Inputs 5 - 8 are referenced to the common connection at pin 4.

Jumper JP1

Sets control mode of the unit to contact closure or remote sensor serial 
data.

Test Switches (PB1 and PB2)

Provides local operation of relays K1 and K2 for testing power circuits or 
motors connected to the relay terminals. An LED indicates relay power 
applied.

Motor Time Delay Potentiometer 
(R8)

Only used in motor control modes. User adjusted for setting relay release 
time between 0 and 90 seconds.

DIP Switch (S2)

Provides selection of control mode options. See Motor Control Mode DIP 
Switch S2 Positions table on page 4 and Control Input Wiring to Connector 
P2 Terminals table on page 4 for control mode settings.

Enclosure

Metal with black matte finish, knockouts for conduit.

Dimension (HWD)

• 8.5" (10.5" including flange) x 4.5" x 2.2"

• (220 mm (270 including flange) x 110 mm x 60 mm)

Weight

3.0 lbs. (1.4 kg) with flange

Options

12 VDC power supply (for 277 VAC applications)

Summary of Contents for UPC20 Plus

Page 1: ...Operation Reference Guide Control System Accessories UPC20 Universal Power Controller Last Revised 09 12 2007...

Page 2: ...liability applies whether damages are sought or a claim is made under this warranty or as a tort claim including negligence and strict product liability a contract claim or any other claim This limita...

Page 3: ...le disconnect device shall be incorporated into the fixed wiring An insulated earthing conductor that is identical in size insulation material and thickness to be earthed and unearthed branch circuit...

Page 4: ......

Page 5: ...wer Control mode 5 Remote Sensor Control mode 5 Channel codes Remote Sensor mode 6 Installation 7 P1 Terminal Connections 7 P2 Terminal Connections 7 Control Mode 7 High Voltage Wiring Options 10 Sing...

Page 6: ...ii UPC20 Universal Power Controller Table of Contents...

Page 7: ...to protect the motor A timing adjustment potentiometer is user adjustable for automatic release of the relays The range is 0 to 90 seconds 1 2 and 3 button control modes are selectable In Power Contr...

Page 8: ...E INSIDE COVER FOR DETAILED WIRING NOTE NO HIGH VOLTAGE THIS CONNECTION AND DIP SWITCH INFORMATION IN 4 8 CONTROL INPUT INPUTS GND 3 DATA 2 GND 4 4 3 IN 1 IN 2 5 6 IN 3 7 CONTACT 12 9 REMOTE C R IND C...

Page 9: ...o theP1 Terminal Connections section on page 7 Set switch S1 to the line input voltage value used before applying power to the UPC20 High Voltage Terminal Block P1 High voltage input and output wiring...

Page 10: ...0 seconds It is typically set to allow direction limit switches to operate or to reach the desired position Single Button Mode operates with one pushbutton in a sequence Up Stop Down Stop and so on fo...

Page 11: ...his allows up to 8 UPC20 and IR sensors to be used in the same room without interfering with one another It is possible to control 2 separate UPC20 s with one handheld remote control The 4th switch of...

Page 12: ...de Sw 1 Sw 2 Sw 3 Sw 4 Radio Code UPC20 Off Off Off Off 0 First On Off Off Off 1 First Off On Off Off 2 First On On Off Off 3 First Off Off On Off 4 First On Off On Off 5 First Off On On Off 6 First O...

Page 13: ...is 20 Amps There are two 12 gauge jumpers that are wired to supply board power at 120 240 VAC and to connect the common terminals of the relays The jumpers are removed as needed according to the wiri...

Page 14: ...d 2 off after time out Motor Momentary Off On Off On Minimum Push 1 load 1 on Release 1 load 1 off Push 2 load 2 on Release 2 load 2 off Maximum Push 1 load 1 on Release 1 load 1 off Note No delay on...

Page 15: ...Push 2 again load 2 off Release 2 again load 2 still off Power Momentary 1 Latch ing 2 Minimum Push 1 load 1 on Release 1 load 1 still on Push 1 again load 1 off Release 1 again load 1 still off Push...

Page 16: ...er Two Button On Off Off On Minimum Push 3 load 1 off Release 3 load 1 still off Push 4 load 2 off Release 4 load 2 off Maximum Push 3 load 1 off Release 3 load 1 still off Push 4 load 2 off Release 4...

Page 17: ...circuit protected and the output supplies up to 25 mA for the remote sensor For dual circuit 277 VAC operation remove both 12 AWG wire jumpers FIG 6 Low voltage and 277 VAC high voltage wiring 1 2 3...