Installation
16
Radia Lighting Control System
Configuring and connecting AXlink
On all AMX Lighting controllers, DIP switch SW1 sets the AXlink device number. The device
number is determined by the value of all the switch position settings. The following table shows the
SW1 DIP switch positions and their values. The device number assignment range is 1 through 255.
1.
Power off the enclosure unit at the breaker panel.
2.
Locate the SW1 DIP switch (AXLINK ADDRESS) on the controller circuit card and set the
device number using the values shown in the proceeding table.
3.
Connect the four-pin AXlink male connector into the four-pin female AXlink connector on the
controller circuit card. FIG. 20 shows how to wire the AXlink connector to a Central
Controller system.
4.
Apply power to the controller module at the breaker panel.
Connecting dry closures
AMX Lighting controller modules contain eight connections for dry contact closures, and one
common reference point. FIG. 21 shows the standard wiring configuration for the 9-pin dry closure
connector.
SW1 DIP switch setting values for AXlink
Position
Value
1
1
2
2
3
4
4
8
5
16
6
32
7
64
8
128
FIG. 20
AXlink wiring diagram
Central Controller
AXlink connector
+12V
AXP/TX
AXM/RX
GND
+12V
AXP
AXM
GND
(optional)